The optional LVD driver lite circuit card contains an LVD inhibit switch and indicator. Refer to Figure 2-4.This card is required for distribution cabinets that contain two LVLD contactors or one LVLD contactor and one LVBD contactor. LVBD contactor must be rated at 600A or lower.

Caution: If the switch is returned to the ON (normal) position when low voltage disconnect alarms are active, a low voltage disconnection will occur.

Warning: While the LVD inhibit switch is in the OFF (inhibit) position, a low voltage disconnection will not occur if battery or load voltage decreases below the low voltage disconnect setpoint. For maximum battery protection, this switch should NOT be left in the OFF (inhibit) position.

J3

J1

J2

 

 

S1

 

 

 

 

Note: The UP position will not close the LVBD contactor

LVD Inhibit

 

 

 

if the battery is manually disconnected using the

 

 

 

Manual Battery Disconnect Switch.

Active Indicator

 

 

 

LVD Inhibit Switch

 

Illuminates when the

Momentary UP / Middle / Down

low voltage disconnect

Momentary UP Position: Closes all LVD Contactors (inhibit mode).

circuit has been disabled

Middle Position: OFF (ACU+ DOES NOT control LVD’s) (inhibit mode).

through the use of the

DOWN Position: ON (ACU+ controls LVD’s).

LVD Inhibit switch.

 

 

 

 

Figure 2-4

Optional LVD Driver Lite Circuit Card (P/N 547873)