UM581127000 User Instructions
Issue AB, March 22, 2012 Spec. No. 581127000 (Model 710NPBA)
Page 6 Chapter 2. Operating Procedures
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Optional LVD Driver Circuit Card
The optional LVD driver circuit card contains an LVD inhibit switch and indicator. Refer to
Figure 2-3. This card is required for 2-, 3-, or 4-row distribution cabinets that contain
three or more LVD contactors (LVBD and/or LVLD); or if the distribution cabinet is
equipped with an LVBD contactor rated 1200A or higher.
Caution: If the switch is returned to the ON (normal) position when low voltage
disconnect alarms are active, a low voltage disconnection will occur.
Warning: While the LVD inhibit switch is in the OFF (inhibit) position, a low
voltage disconnection will not occur if battery or load voltage decreases
below the low voltage disconnect setpoint. For maximum battery
protection, this switch should NOT be left in the OFF (inhibit) position.
Figure 2-3
Optional LVD Driver Circuit Card (P/N 540972)
LVDInhibit Switch
MomentaryUP / Middle / Down
MomentaryUP Position: Closes all LVD Contactors (inhibit mode).
MiddlePosition : OFF (ACU+ DOES NOT control LVDs) (inhibit mode).
DOWNP osition: ON(ACU+ controls LVDs).
LVDInhibit
ActiveIndi cator
Illuminates when the
lowvo ltage disconnect
circuit has been disabled
through the use of the
LVDInhibit switch.
J6 J5 J4
J3 J2 J1
J9
J7
S1
Note:The UP position will not close the LVBD contactor
ifthe battery is manually disconnected using the
ManualBattery Disconnect Switch.