User Instructions | UM581127000 |
Spec. No. 581127000 (Model 710NPBA) | Issue AB, March 22, 2012 |
|
|
Replacing a Battery or Load Disconnect Contactor
Danger: All sources of AC and DC power must be completely disconnected from this power system before performing this procedure. Use a voltmeter to verify no DC voltage is present on the system busbars before proceeding.
Note: In the following procedure, before making
Procedure
Note: Refer to Figure
Removing the Contactor
1)Verify all AC and DC power sources are disconnected from the power system.
2)For the
3)For the 2, 3, or
4)Disconnect the wiring to the contactor by unplugging the quick disconnects.
5)Note the orientation of the contactor to ensure the replacement is installed the same way. Unbolt the contactor
Installing the Replacement Contactor
1)Position the replacement contactor oriented the same way as the old.
2)Secure the contactor with the hardware removed above. Refer to Figure
3)Replace the wiring to the contactor by
4)For the 2, 3, or
Restarting the Power System
1)Reconnect the AC and DC power sources to the power system.
2)Start the power system. Refer to the separate Installation Instructions (IM581127000) for a startup procedure.
3)Verify no alarms are active.
Chapter 4. Troubleshooting and Repair | Page 47 |