User Instructions UM581127000
Spec. No. 581127000 (Model 710NPBA) Issue AB, March 22, 2012
Chapter 4. Troubleshooting and Repair Page 51
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-20
Replacing a Load Disconnect Contactor
in a 2, 3, or 4-Row Distribution Cabinet
LoadDisconnect
Contactor
2-rowDistribution Cabinet
shown,3 or 4-row ca binet similar.
Applyelectrical anti-oxidizing
compoundto busbar
matingsurfaces.
5/16-18Nut
5/16"Belleville Lock Washer
5/16"Belleville Lock Washer
(concaveside of Belleville
LockWashers face each other)
5/16"Hardened Flat Washer
(4places)
Torqueto 100 in-lbs.
Componentsremoved in
illustrationfor clarity only.
Front
Contactorstyles vary
betweenmanufacturer s.
BlackWire
Violet/WhiteWire
VioletWire
RedWire
Violet/WhiteWire
VioletWire BlackWire
RedWire