Installation and Setup Guide
Sounder (Bell) Connections
Basic Connections
3 4
ALARM OUTPUT |
|
10.5 - 13.5 VDC |
|
2A MAX. | V0 |
| spkr |
Make sounder connections to alarm output terminals 3 (+) and 4
•The 12VDC sounder output activates when an alarm occurs.
•Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will overload the power supply, or may cause the electronic circuit protecting the sounder output to trip).
•You must install a battery, since the battery supplies this current.
Supervised output
1.Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the PC board.
2.Connect a 2k ohm resistor across the terminals of the last sounder. See Figure 5.
This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses – pause – 3
UL
•Use only UL Listed sounding devices for UL installations.
•Bell supervision is required for fire alarm installations.
•The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600 mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate in a
TERMINALS ON | EXTERNAL ALARM |
|
|
CONTROL BOARD | SOUNDER |
|
|
4 |
|
|
|
ALARM |
| 2000 |
|
OBSERVE | OHM |
| |
OUTPUT |
| ||
POLARITY | EOL |
| |
TERMINALS |
| ||
+ | RESISTOR | ||
+ |
| ||
|
|
| |
3 |
|
|
|
2 | IF BELL SUPERVISION IS ENABLED |
|
|
|
|
| |
| (RED JUMPER ON CONTROL BOARD IS CUT) |
| |
| CONNECT A 2000 OHM RESISTOR ACROSS | ||
| THE EXTERNAL SOUNDER AS SHOWN BY | ||
CUT RED JUMPER ON CONTROL | THE DOTTED LINE. |
| 001- |
|
| sounder | |
BOARD TO ENABLE BELL | DO NOT CONNECT THE RESISTOR AT THE | ||
(SOUNDER) SUPERVISION. | ALARM OUTPUT TERMINALS THEMSELVES! |
Figure 5. Sounder Wiring (Supervised)
Connecting the Keypads and Other Addressable Devices
Connections
|
| 4 _ | |
|
|
| 5 + |
|
|
| 6 IN |
|
|
| 7 OUT |
BLACK | RED | GREEN | YELLOW |
AR |
|
|
|
MED |
|
|
|
READY |
|
|
|
|
|
|
Connect keypads and other addressable devices (4204, 4219, 4229, 4286, 5881, LRR, etc.) to the control’s keypad terminals as shown on the Summary of Connections diagram. The system supports up to 8 keypads, which can be assigned to partitions in any combination (see program fields
Determine wire size using the Wire Run Chart on the following page. For single
Supplementary Power (optional)
UL Use a UL Listed,
The
Use supplementary power if the control’s aux. power load for all devices exceeds 600mA (suggested power supply: AD12612). Connect as shown in Figure 6. Be sure to connect the negative
IMPORTANT: Keypads powered from supplies that do not have a backup battery will not function if AC power is lost. Make sure to power at least one keypad in each partition from the control’s auxiliary power output.
SUPPLEMENTARY |
| CONTROL TERMINAL STRIP | |||||||
POWER SUPPLY |
| ||||||||
|
|
|
|
|
|
|
| ||
+ | – |
| AUX. AUX. DATA DATA | ||||||
|
|
|
| – | + |
| IN | OUT | |
|
|
| 4 | 5 | 6 | 7 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
REDWIRE | WIREBLK | GRNWIRE | WIREYEL | DIRECTLY TO | WIREBLK | REDWIRE | GRNWIRE | WIREYEL |
| |
|
|
|
| IMPORTANT: |
|
|
|
|
| |
|
|
|
| MAKE THESE |
|
|
|
|
| |
KEYPADTO | KEYPADTO | KEYPADTO | KEYPADTO | CONNECTIONS | KEYPADTO | KEYPADTO | KEYPADTO | KEYPADTO | ||
SCREW | ||||||||||
|
|
|
|
|
|
|
|
| ||
|
|
|
| TERMINALS AS |
|
|
|
|
| |
|
|
|
| SHOWN. |
|
|
|
|
|