Installation and Setup Guide

Enter Output No.

R0202

Output Number

01-16 = VISTA-20P output no.; 01-08 = VISTA-15P output no.; 17-18 = on-board triggers Enter the device output number (programmed in *79 Menu Mode) you want associated with this output. Press [] to continue.

02A E P TRIG

R02 1 1 3 ZL=00

Summary Screen

A summary screen appears showing the programmed settings. Press [] to continue.

About Zone Lists (*81 Menu Mode)

Zone lists let you group individual zones for use with certain system actions. The following table shows the available zone lists and their purposes:

List No.

 

Used for…

Notes

1, 2

general purpose (GP)

• Any list may include any or all of the system's zone

3

 

chime-by-zone(see field *26 to enable option)

numbers.

4

cross zones (see note at right)

• A zone list can be assigned to more than one output relay.

5

night stay zones

• Zone List 4: When creating zone list 4 for cross zoning,

6

 

general purpose

include only zones assigned to zone types 3, 4, or 5. Do not

 

 

V20PSIA/V15PSIA

: dial delay disable

include zones that have delays (entry/exit zones, interior

7

 

general purpose

w/delay) or 24-hour zones, as these zone types may produce

 

 

V20PSIA/V15PSIA

: unlimited reports

unpredictable operation and may not function as intended.

8

 

general purpose

See field *85 for Cross Zone Timer option.

9

zones that activate Pager 1

• Zone List 6:

V20PSIA/V15PSIA

: See field *50 for Dial Delay

10

zones that activate Pager 2

Disable option.

11

zones that activate Pager 3 (VISTA-20P)

• Zone List 7:

V20PSIA/V15PSIA

: See field *93 for Unlimited

12

zones that activate Pager 4 (VISTA-20P)

Reports option.

Zone List Programming

1.Select an appropriate zone list number.

2.Add the desired zone numbers to be included in that list.

Start Zone List Program Mode by pressing 81 while in Data Programming mode.

*81 Menu Mode

 

 

 

Zone List Number

 

Zone List No.

 

 

 

01-12 = zone list number; [] to continue

 

(00 = Quit)

01

 

Enter the Zone List Number to program (or 00 to quit). Press [] to advance.

 

 

 

 

 

 

In the following displays, zone list 01 has been selected for programming.

 

 

 

Zone Number

 

01 Enter Zn Num.

 

01-64= zone numbers followed by [] to accept each zone; 00 to continue

 

(00 = Quit)

00

 

Enter each zone number to add to the zone list, followed by pressing [] (example, 01,

 

 

 

 

 

 

 

 

 

02, 03). After all zones are entered, press 00 to continue.

 

 

 

IMPORTANT: Do not include fire zones in zone lists that are used to STOP device actions.

 

 

 

VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56.

01 Del Zn List?

Deleting Zone Lists

0 = don’t delete list; 1 = delete this zone list; [] to continue

0 = No 1 = Yes 0

To delete the zone list, enter 1. All zones in the zone list will be deleted automatically and

 

the system returns to the Zone List No. prompt. To save the zone list, enter 0.

01 Delete Zone?

0 = No 1 = Yes 0

Deleting a Zone

0 = don’t delete zones; 1 = go to next prompt to delete zones; [] to continue

To save the zone list, enter 0 and the system returns to the Zone List No. prompt. To delete a zone or zones in a zone list, enter 1 to continue.

01 Zn to Delete?

 

(00 = Quit)

00

Delete the Zone

01-64= zones to be deleted from list followed by [] to accept each zone; 00 to continue Enter each zone to be deleted from the list, followed by []. After all zones to be deleted are entered, enter 00 to return to the Zone List No. prompt so that another list can be programmed, if desired.

VISTA-20P = 01-64; VISTA-15P = 01-06, 09-34, 49-56.

5-12

Page 48
Image 48
Honeywell VISTA-20PSIA, VISTA-15PSIA setup guide About Zone Lists *81 Menu Mode, Zone List Programming