Table 6 Harmful gas limits in an equipment room
Gas | Max. (mg/m3) |
SO2 | 0.2 |
|
|
H2S | 0.006 |
NH3 | 0.05 |
|
|
Cl2 | 0.01 |
Fan trays of the routers are hot swappable and support automatic fan speed adjustment. To ensure good ventilation, the following requirements must be met:
•Leave at least 10 cm (3.94 in) of clearance at the inlet and outlet air vents.
•The installation site has a good cooling system.
Figure 2 Airflow through the HSR6804 chassis
NOTE:
An HSR6802 router uses the same airflow system as an HSR6804 router.