Appendix D Cable management
When the router is mounted in a
General cabling requirements
Minimum curvature radius of cables
•The curvature radius of a fixed power cable, communication cable, or ribbon cable should be at least five times the cable's outer diameter. If the cable is frequently bent, plugged, and unplugged, the curvature radius should be at least seven times the cable's outer diameter.
•The curvature radius of an ordinary fixed coaxial cable should be at least seven times of the cable's outer diameter. If the coaxial cable is frequently bent, plugged, and unplugged, the curvature radius should be at least 10 times the cable's outer diameter.
•The curvature radius of a
Minimum curvature radius of fibers
•When the fiber is wrapped up around the cabling plate, the diameter of the cabling plate should be at least 25 times the fiber's diameter.
•When the fiber is being moved, the curvature radius of the fiber should be at least 20 times the fiber's diameter.
•When the fiber is fixed, the curvature radius of the fiber should be at least 10 times the fiber's diameter.
NOTE:
The fiber's diameter refers to the diameter of the fiber jacket. Typically, the diameter of a
Labeling cables
Label cables before you route or bundle them. Labels are typically affixed 20 mm (0.79 in) to cable plugs.