HP Performance Optimized Data Center (POD) 40cp manual Water quality requirements

Models: Performance Optimized Data Center (POD) 40cp

1 63
Download 63 pages 13.75 Kb
Page 30
Image 30

Water quality requirements

Water quality requirements and specifications

Closed-loop water must not contain any lime scale deposits or loose debris.

The water must have a low level of hardness, particularly a low level of carbon hardness. Additionally, the water must not be so soft that it attacks the materials with which it comes into contact.

The chilled water temperature to be supplied to the HP POD is 12º to 24ºC (55º to 75ºF). Freezing water might cause a blockage and damage to the unit. In outside locations subject to freezing temperatures, an additive such as glycol might be necessary to lower the freezing point. However, the heat transfer potential of the water is lower, so the equipment must be derated properly.

Acceptable water quality specifications

Water must be maintained per the following acceptable water quality standards.

Parameter

Range

 

 

pH

8.0–10

 

 

Specific conductance at 25ºC

0–2500 µmhos/cm

(77ºF)

 

 

 

Alkalinity ("M" as CaCO3)

150–1000 ppm

Sulfur (SO4)

0–150 ppm

Chloride (Cl)

0–100 ppm

 

 

Hardness (CaCO3)

0–350 ppm

Calcium hardness (CaCO3)

0–200 ppm

Magnesium hardness (CaCO3)

0–150 ppm

Copper (Cu)

< 0.20 ppm

 

 

Iron (Fe)

< 3.0 ppm

 

 

Aluminum (Al)

< 0.50 ppm

 

 

Sodium (Na)

0–1000 ppm

 

 

Silica (SiO2)

0–150 ppm

Zinc (Zn)

< 1.0 ppm

 

 

Manganese (Mn)

< 0.1 ppm

 

 

Phosphate Ortho- (PO4)

< 3 ppm

Bacteria

< 1000 CFU/ml

 

 

Suspended solids

< 10 ppm

 

 

If your water is out of range, consult a water quality expert.

Water quality requirements 30

Page 30
Image 30
HP Performance Optimized Data Center (POD) 40cp manual Water quality requirements and specifications