Panels

The following panels are on the exterior of the HP POD.

Item

Component

Description

 

 

 

1

Electrical busway enclosed

400A enclosed circuit breakers that powers the electrical

 

circuit breaker (on page 36)

busways:

 

 

Two electrical busway panels are activated in the

 

 

standard HP POD.

 

 

Three electrical busway panels are activated in the high

 

 

density HP POD.

 

 

 

2

EPO panel (on page 36)

Contains controls and status indicators for the EPO system

 

 

 

3

Fire alarm panel ("Fire alarm

Contains controls and status indicators for the fire alarm

 

control panel" on page 38)

system

 

 

 

4

ASSD panel (on page 36)

Air sampling smoke detection system

 

 

 

5

EPO button

Cuts off all power to the POD and activates the EPO alarm

 

 

lamp.

 

 

 

6

Security panel ("Security panel

Reserved for installing interface and power requirements for

 

location" on page 39)

any optional security devices installed.

 

 

 

7

EPMS panel("EPMS panel"

Electrical power monitoring system

 

on page 38)

 

 

 

 

8

Humidifier ("Humidifier

Maintains the humidity inside the HP POD within a set range

 

(optional)" on page 44)*

to minimize static electricity.

 

 

 

9

Auxiliary Land power*

Provides auxiliary power for the BMS or convenience outlets.

 

 

120V owner-provided power.

 

 

 

10

BMS panel (on page 36)

Building Management System

 

 

 

11

Fan control (FC) panel ("Fan

Circuit breakers that control the fan units

 

control panel" on page 38)

 

 

 

 

12

House panel (on page 38)

120A electrical panel board providing auxiliary HP POD

 

 

electrical requirements

 

 

 

13

Junction Box

Main input box for incoming electrical feeder cables

 

 

 

Optional component

 

Power management 35