The high density HP POD includes an additional electrical busway in the center of the unit.

High density HP POD

Feature

Specification

 

 

Number of busways

3

 

 

Frequency

60Hz

 

 

Amps (per breaker)

400A

 

 

Neutral Ampacity (per breaker)

480A

 

 

Amps derated percentage

20%

 

 

Max usable amps (per busway)

320A

 

 

Voltage (per busway)

415V

 

 

Grounding

Aluminum casing

 

 

Phases

3

 

 

Rack power

Power is provided to each of the rack by PDUs. The PDUs can be moved around the HP POD to support component power requirements. The PDUs are powered by the drop boxes attached to each electrical busway.

For more information regarding power shortages to the PDUs or electrical busway drop boxes, see Troubleshooting (on page 49).

Power management 34