Troubleshooting

HP POD troubleshooting

Issue

Resolution

 

 

The water is not flowing, or flowing too

Verify that all applicable valves are open. Inspect the water

slowly.

lines for blockage, unblock, or replace them as necessary.

 

 

The HP POD is overheating.

If the fan is not functioning, check the integrity of the electrical

 

connection to the fan. If the electrical connection seems OK,

 

replace the fan.

 

If the fan is functioning, check for a kink or blockage in the

 

water line to the heat exchanger.

 

Contact HP service.

 

 

The strobe lights are flashing.

Either the EPO or the fire alarm system has been activated. Get

 

out of the HP POD immediately and follow standard emergency

 

procedures for your facility.

 

 

There is a leak inside the HP POD.

Locate and note the source of the leak. Prevent the leaking

 

water from contacting any electrical equipment. Repair the leak

 

as soon as possible.

 

 

There is no power to one rack.

1 Verify that the racks on either side of the rack have power.

 

2 Check the status of the busway dropbox for that rack.

 

If a breaker has tripped, reset the breaker box and verify

 

that power has been restored to the rack.

 

If none of the busway dropbox breakers has tripped, check

 

the status of the PDUs for the rack. If the input or output

 

breakers have tripped, reset the PDU and verify that power

 

has been restored to the rack.

 

If none of the breakers on the busway dropbox or PDUs

 

have tripped, replace the busway dropbox.

 

 

There is no power to multiple racks.

1 Verify that the HP POD is receiving power.

 

2 Check the status of each of the electrical busway panels. If

 

one of the breakers has tripped, reset the breaker and verify

 

that power has been restored to the racks.

 

3 Check the status of the connection transformer and

 

switchboard. If one of the breakers has tripped, reset the

 

breaker and verify that power has been restored to the

 

racks.

 

 

There is no power to the HP POD.

Check the status of the connection transformer and switchboard.

 

If one of the breakers has tripped, reset the breaker and verify

 

that power has been restored to the HP POD.

 

 

Troubleshooting 49