Feature

Humidifier

Specification

3.79l/hr (1 gal/hr) domestic water from an alternate supply source

Rack specifications

Standard HP POD racks (AN982A)

Feature

Specification

 

 

U height

50U

 

 

Width

56-mm

 

 

Depth

1,000-mm

 

 

Maximum load weight

3,000 lb

 

 

International shock-mounted HP POD racks (AT052A)

Feature

Specification

 

 

U height

46U

 

 

Width

56-mm

 

 

Depth

1,000-mm

 

 

Maximum load weight

2,760 lb

 

 

Thermal and air flow performance

Maximum thermal and air flow

HP POD specification

performance parameters

 

 

 

Air temperature—Inlet to rack-

Cold aisle setpoint temperature in BMS

mounted components

 

 

 

Chilled water temperature

12°–19°C (55°–65°F)

 

 

Total rack-mounted component air

Variable as required to maintain cold

flow

aisle setpoint temperature

 

 

Chilled water flow rate

240 gal/min (908 l/min) without

 

utility module

 

280 gal/min (1,060 l/min) with

 

utility module

 

 

Chilled water pressure differential at

5 psi max

flow needed to meet thermal

 

specifications

 

 

 

Server heat load

450 kW standard HP POD

 

605 kW high density HP POD

 

 

Specifications 52

Page 52
Image 52
HP Performance Optimized Data Center (POD) 40cp manual Rack specifications, Thermal and air flow performance