Specifications

HP POD specifications

Features

Specifications

 

 

Dimensions

40 ft x 8 ft x 9.5 ft

 

 

Maximum weight

30,000 lb (empty)- 101,000 lb (fully-loaded)

 

 

Maximum power/ cooling

450 kW (Standard POD)

 

605 kW (High density POD)

 

 

Maximum rack quantity

22 racks

 

 

Rack Units (RU) per rack

50 RU

 

 

Rack Units (RU) maximum

1100 RU

 

 

Nominal power/ cooling per rack

25 kW

 

 

Maximum power/ cooling per rack

35 kW

 

 

Power input voltage

415 VAC, 3 Phase, 50/60 Hz, with neutral

 

 

Power distributed internally

Through 2 400A electrical busways

 

240/415 VAC, 50/60 Hz

 

 

Customer access

Double-door on one end

 

Two 3 ft x 7 ft doors to the cold aisle (customer access)

 

Four 6 ft x 7 ft doors to the hot aisle (rear component access)

 

 

Network supported

Bulk cable pass-through-fiber

 

Bulk cable pass-through-copper

 

(Optional) External rated DEMARC box

 

 

Electrical specifications

Panel information

Feature

Electrical busway panel

House panel

 

 

 

 

Number of panels

2

(Standard HP POD)

1

 

3

(High density HP POD)

 

 

 

 

Amps (per panel)

400A

225A

 

 

 

 

Poles (per panel)

1

 

30–42

 

 

 

 

Phases

3

 

3

 

 

 

 

Circuit breaker information (Input)

Specifications 50

Page 50