To disable power to a single PDU, turn off the main switch on that PDU.

To disable power to a single rack, open the main breaker on the dropbox connected to the electrical busway.

To disable power to a single electrical busway, open the appropriate main breaker for that busway on the corresponding electrical busway panel outside of the HP POD.

Power distribution

The standard HP POD is powered by two electrical busways on the ends of the unit.

Standard HP POD

Feature

Specification

 

 

Number of busways

2

 

 

Frequency

60Hz

 

 

Amps (per busway)

400A

 

 

Neutral Ampacity (per breaker)

480A

 

 

Amps derated percentage

20%

 

 

Max usable amps (per busway)

320A

 

 

Voltage (per busway)

415V

 

 

Grounding

Aluminum casing

 

 

Phases

3

 

 

Power management 33

Page 33