Maintenance

Periodic maintenance

Perform periodic inspections of the POD to ensure there is no sign of overheating. During periodic inspections, pay special attention to electrical connections and wiring.

Electrical busway maintenance

Periodically tighten the electrical busway connections. HP recommends tightening the electrical busway connections every six months.

Inspect the busway drop boxes for loose connections, and tighten if necessary.

Water system maintenance

HP does not maintain your water system quality.

Consult a water treatment specialist to perform the following maintenance:

Flush the HP POD

How often you must flush the HP POD depends on how often you shutdown the HP POD and the water quality.

Maintain water quality

The water treatment specialist should periodically take a water sample and add new chemical treatments to the HP POD water or water distribution kit as needed to maintain the specified water quality ("Water quality requirements" on page 30).

Air filter replacement

There are twelve 14 in x 36 in x 1 in air filters inside the HP POD.

If you have the optional air filter sensor (on page 44) installed, you will be notified through your BMS when you need to change a filter.

If you do not have the sensor installed, HP recommends periodically inspecting and changing each air filter.

Air and water heat exchanger maintenance

The air and water heat exchanger requires no maintenance. If particulates are present in the cooling water, a filter must be fitted immediately upstream from the water inlet fittings. Check the functionality of the condensation drainage system regularly. Regularly perform visual inspections for leaks (annually).

Maintenance 54