Environmental specifications

Features

Specifications

 

 

Operating temperature

-18ºC to 54ºC (0ºF to 130ºF)

 

 

Non-operating

2ºC to 54ºC (35ºF to 130ºF)

temperature*

 

 

 

Transit temperature**

-30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours

 

 

Operating humidity

15% to 80% relative noncondensing

 

26ºC (79ºF) maximum wet bulb temperature

 

 

Non-operating humidity*

5 to 95% relative noncondensing

 

39ºC (102ºF) maximum wet bulb temperature

 

 

Operating altitude

-76.2 to 3,048 m (-250 to 10,000 ft)

 

 

Non-operating altitude

-76.2 to 9,144 m (-250 to 30,000 ft)

 

 

*For non-operating specifications, consider the temperature of computer and IT equipment inside the HP POD. **The HP POD must be drained before it is moved to a new location.

For areas prone to freezing, consult HP for applicable operating solutions and evaluate water lines as described in the Frost damage (on page 31) section of this document.

Water distribution kit specifications

Feature

Specification

 

 

Dimensions

10 ft x 8 ft x 9 ft

 

 

Tank capacity

7.8 gal

 

 

Pumps electrical

480V, 3-phase, 60 Hz

 

 

Pumps flow

240 gal/min

 

 

Chemical pot feeder

10 gal

capacity

 

 

 

For more information, see Water specifications (on page 51).

Specifications 53