Feature

Specification

 

 

Number of input circuit breakers

2: 1 per panel

 

 

Protection percentage

80%

 

 

Amps (per breaker)

400A

 

 

Fire alarm panel connections

The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the

HP POD.

Water specifications

Water supply specifications without a water distribution kit

Feature

Specification

 

 

 

Facility input temperature to HP POD

12º to 24ºC (55º to 75ºF)

 

 

 

Operating pressure

137,895 to 172,369 Pa (20 to

 

25 psi)

 

 

 

Rated pressure max

1,034,213 Pa (150 psi)

 

 

 

HP POD pressure drop

110,316 Pa (16 psi)

 

 

 

HP POD water flow rate

908.5 l/min (240 gal/min)

 

 

 

Cooling water supply and return

(2) 10.16 cm (4 inch) 150#

connections

flange

 

 

 

Humidifier

3.79 l/hr (1 gal/hr) domestic

 

water from an alternate supply

 

source

 

 

 

Water supply specifications with a water distribution kit

 

 

 

Feature

 

Specification

 

 

 

Facility input temperature to the water

 

4º to 10ºC (40º to 50ºF)

distribution kit

 

 

 

 

 

Water distribution kit temperature output to

 

12º to 24ºC (55º to 75ºF)

the HP POD

 

 

 

 

 

Operating pressure

 

137,895 to 172,369 Pa (20

 

 

to 25 psi)

 

 

 

Rated pressure max

 

1,034,213 Pa (150 psi)

 

 

 

HP POD pressure drop

 

110,316 Pa (16 psi)

 

 

 

Water distribution kit pressure drop

 

34,474 Pa (5 psi) max

 

 

 

Water flow rate to the water distribution kit

 

757 to 1,893 l/min (200 to

 

 

500 gal/min) based on a

 

 

facility operating delta T

 

 

range of 6°to 12°C (10º–

 

 

20ºF)

 

 

Water distribution kit flow rate to the HP POD

908.5 l/min (240 gal/min)

 

 

Cooling water supply and return connections

(2) 10.16 cm (4 inch) 150#

 

 

flange

 

 

 

Specifications 51