Operation

Front Panel LEDs

The front panel has five LEDs that indicate the status of the UPS.

1 2 3 4 5

Figure 2-3: Front panel LED display

Item

Description Symbol

Meaning

1

Utility

Solid greenNormal operation

 

 

 

 

 

 

 

 

 

Rapidly flashing green—Ramp Up mode

 

 

 

 

 

 

 

 

 

Slowly flashing greenStandby mode (batteries charging)

2

Battery

 

 

 

 

 

 

 

Solid amberOn Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing amberBattery test in progress

 

 

 

 

 

 

 

 

 

3

Bypass

Solid amberOn Bypass

 

 

 

 

 

 

 

 

 

Flashing amber—Bypass not available

4

Alarm

Solid redOne or more alarms may be present or active

5

Redundant

Solid greenN+1 mode (one or more redundant electronics

 

 

 

 

 

 

 

 

 

modules operating in system)

Flashing green—Battery self-test initiated

OffNon-redundant, not N+1 mode

NOTE: The LED lights cycle when no electronics modules are installed and utility is present. In Standby mode, there is no output but the batteries will be charging. The time required to reach Standby mode can range from 45 seconds to several minutes, depending on the state of charge of the batteries.

HP Uninterruptible Power System R12000 XR Models User Guide

2-3