Troubleshooting
Table
LCD Display | Possible Cause | Suggested Action |
x Alarms | This alarm is triggered by one of the | |
| following events: | |
Inverter Startup | ||
| ||
Failure | • The UPS detects that at least one | |
| electronics module failed to | |
| complete its startup sequence as | |
| expected and was most likely shut | |
| down. In this situation, the alarm is | |
| more of a general status indicator. | |
| It should be accompanied by | |
| another alarm, indicating the | |
| reason for the modules failure to | |
| start. | |
| • An electronics module has briefly | |
| (for approximately | |
| second) disconnected from the | |
| system and is attempting to restart. | |
| In this situation, no other alarms | |
| associated with this failure will | |
| occur, with the exception of a | |
| possible Internal Communications | |
| Failure alarm. |
The electronics module may not be fully seated. Remove the bezels and ensure that each of the electronics modules is fully inserted into the chassis.
Contact Technical Support for assistance.
xAlarms
Inverter
Uncalibrated
At least one electronics module has not been calibrated together as a set, which is required for efficient
An autocalibration is required, and the UPS will automatically schedule the autocalibration process on detection of this condition.
Contact Technical Support for assistance.
x Alarms | The UPS detects that the current load | Reduce the load level to clear the | |
| has exceeded 102% of the maximum | alarm. If the alarm persists after load | |
Level 2 Overload – | |||
capacity available, which means it is | reduction, see the LCD panel to | ||
Phase A | |||
operating in Nonredundant mode. | determine which electronics module is | ||
| |||
| The UPS will transfer to Bypass mode | reporting overload. | |
|
| ||
| after two minutes of this sustained load | Contact Technical Support for | |
| level. | assistance. | |
|
|
| |
x Alarms | The UPS detects that the current load | Reduce the load level to clear the | |
| has exceeded 110% of the maximum | alarm. If the alarm persists after load | |
Level 3 Overload – | |||
capacity available, which means it is | reduction, see the LCD panel to | ||
Phase A | |||
operating in Nonredundant mode. | determine which electronics module is | ||
| |||
| The UPS will transfer to Bypass mode | reporting overload. | |
|
| ||
| after 30 seconds of this sustained load | Contact Technical Support for | |
| level. | assistance. | |
|
|
| |
|
| continued |
HP Uninterruptible Power System R12000 XR Models User Guide |