Specifications

Battery Specifications

Table C-4: Battery Specifications

Feature

Specification

Type

Each module contains maintenance-free, sealed, valve

 

regulated lead-acid (VRLA) batteries with an eight-year

 

minimum float service life at 25°C (77°F).

 

 

Voltage

The battery module has a battery string voltage of

 

48 Vdc.

 

 

Charging

Complete charge takes no more than 48 hours.

 

The UPS recharges in three hours to 80% usable

 

capacity.

 

ERMs will recharge in less than eight hours to 80%

 

usable capacity.

 

 

Battery Runtime

Table C-5: Estimated Battery Runtime

Load

Estimated Battery

UPS with ERM

(Percent)

Runtime (Minutes)

Runtime (Minutes)

 

 

 

20

43

69

 

 

 

50

14

28

 

 

 

80

7

15

 

 

 

100

5

11

 

 

 

Environmental Specifications

Table C-6: Environmental Specifications

Feature

Specification

Operating temperature

10oC to 40oC (50oF to 104oF)

 

UL-tested at 25oC (77oF)

 

 

Relative humidity

0% to 95%; non-condensing

 

 

Operating altitude

Up to 2,000 m (6,562 ft) above sea level

 

 

Audible noise

Typically 60 dBA

 

 

Transit temperature

-25oC to +55oC (-13oF to 131oF)

 

 

Transit altitude

15,000 m (49,212 ft) above sea level

 

 

HP Uninterruptible Power System R12000 XR Models User Guide

C-3