Troubleshooting
Table
LCD Display | Possible Cause | Suggested Action | |
x Alarms | At least one electronics module | Contact Technical Support for | |
| generates this alarm when it detects an | assistance. | |
Rectifier Input | |||
abnormally high input current. The |
| ||
Over Current |
| ||
detecting module shuts down to protect |
| ||
|
| ||
| itself from damage. The UPS may have |
| |
| transitioned into Automatic Bypass |
| |
| mode due to the failure, depending on |
| |
| the load levels present at the time of |
| |
| the failure and the number of modules |
| |
| affected. |
| |
| This could be caused by a hardware |
| |
| failure. |
| |
|
|
| |
x Alarms | The UPS detects a Remote Emergency | Refer to the section, “Remote | |
| Power Off signal. The electronics | Emergency Power Off Port,” in | |
Remote | |||
modules immediately shut down and | Chapter 1 for more information. | ||
Emergency Power | |||
battery starts are inhibited. |
| ||
Off |
| ||
|
| ||
|
|
| |
x Alarms | At least one electronics module failed | Contact Technical Support for | |
| the code validation check. The code | assistance. | |
Software | |||
revision currently installed is |
| ||
Incompatibility |
| ||
incompatible with the rest of the |
| ||
Detected |
| ||
system. |
| ||
|
| ||
|
|
| |
x Alarms | This is an alarm and a status to | This is a normal operation. This alarm | |
| indicate that the UPS is currently | may be accompanied by other alarms | |
UPS On Battery | |||
operating in Battery mode. | that will indicate the root cause of the | ||
| |||
|
| problem. | |
|
|
| |
x Alarms | This is an alarm and a status to | This alarm may be accompanied by | |
| indicate that the UPS is currently | other alarms that will indicate the root | |
UPS On Bypass | |||
operating in Bypass mode. | cause of the problem. | ||
| |||
|
|
| |
x Alarms | The UPS detects that the utility source | Verify the utility power. If the problem | |
| voltage is not within an acceptable | persists, contact an electrician. | |
Utility Fail | |||
range. |
| ||
|
| ||
|
|
| |
x Alarms | The UPS detects that the utility source | Verify the utility power. If the problem | |
| voltage is either not present, or so | persists, contact an electrician. | |
Utility Not Present | |||
abnormally low that the UPS classifies |
| ||
|
| ||
| it as not being present. |
| |
|
|
|
HP Uninterruptible Power System R12000 XR Models User Guide |