| Troubleshooting | |
| Table |
|
| ||
| Symptom | Possible Cause | Suggested Action | ||
|
|
|
|
| |
| All LEDs flash on and off | Autocalibration is in process. | Wait for continuous Utility | ||
| together. |
| LED. | ||
|
|
|
|
| |
| Redundant LED and audible | Redundancy mode is not | Reduce output load to allow | ||
| alarm frequently turn on and | available. | system to remain in | ||
| off. |
| Redundancy mode. | ||
|
|
|
|
| |
| Audible alarm sounds. | UPS is on bypass. | Do one of the following: | ||
| Bypass LED and Alarm LED |
| • Scroll through the LCD | ||
| are lit. |
|
| menu to view current | |
|
|
|
| alarms. | |
|
|
| • | Use the power | |
|
|
|
| management software to | |
|
|
|
| view the alarm history to | |
|
|
|
| determine the reason for | |
|
|
|
| the transfer to Bypass | |
|
|
|
| mode. | |
|
|
|
|
| |
| Audible alarm sounds. | UPS is on battery. | Do one of the following: | ||
| Battery LED and Alarm LED |
| • Scroll through the LCD | ||
| are lit. |
|
| menu to view current | |
| Redundant LED is off. |
|
| alarms. | |
|
|
|
|
| |
|
|
| • | Use the power | |
|
|
|
| management software to | |
|
|
|
| view the alarm history to | |
|
|
|
| determine the reason for | |
|
|
|
| the transfer to Battery | |
|
|
|
| mode. | |
|
|
|
|
| |
| Audible alarm sounds. | UPS is on battery. | Do one of the following: | ||
| Battery LED, Alarm LED, and |
| • Scroll through the LCD | ||
| Redundant LED are lit. |
|
| menu to view current | |
|
|
|
| alarms. | |
|
|
| • | Use the power | |
|
|
|
| management software to | |
|
|
|
| view the alarm history to | |
|
|
|
| determine the reason for |
the transfer to Battery mode.
continued
HP Uninterruptible Power System R12000 XR Models User Guide |