LCD Configuration and Status

Choose the baud rate for the selected serial port or option slot.

Table 3-9: Baud Rate Setup

LCD Display

Explanation

Baud Rate

x

Choose the baud rate for the serial port or option slot selected above. Here, x is the baud rate and can be equal to 1200, 2400, 4800, 9600 (default) or 19200.

An asterisk (*) indicates the current baud rate.

Setting the Voltage

Select Set Voltage from the System Setup menu to set the voltage. The asterisk (*) indicates the current configuration. The options for voltage are 200, 208, 220, 230 (default), and 240.

System Setup

Set Voltage

NOTE: This option is only available when the UPS is in Standby mode or Manual Bypass mode. Otherwise, the LCD panel indicates Not Available.

Setting the Hardware Configuration

Select Set HW Config from the System Setup menu to set the hardware configuration for the UPS.

System Setup

Set HW Config

Table 3-10: Hardware Configuration Choices

LCD Display

Explanation

Set HW Config

Select this option to configure the number of ERMs

 

installed.

ERM Setup

 

 

 

Set HW Config

Select this option to enable a battery commissioning test.

 

 

Commission Battery

 

 

 

Set HW Config

Select this option to go to the Parallel Mode menu options.

 

 

Parallel Mode

 

 

 

HP Uninterruptible Power System R12000 XR Models User Guide

3-13