Troubleshooting
Table
LCD Display | Possible Cause | Suggested Action | |
x Alarms | The UPS detects that one or more of | Contact Technical Support for | |
| the internal module fuses has failed. | assistance. | |
Fuse Failure | |||
|
| ||
|
|
| |
x Alarms | An electronics module detects a | Check the ventilation grills for | |
| heatsink over temperature condition. | blockage. If the grills are blocked, | |
Heatsink Over | |||
The detecting module immediately | remove blockage, switch to | ||
Temperature | |||
shuts down to protect its heat sensitive | Maintenance Bypass mode, and restart | ||
| |||
| components. | the system. Verify that the ambient | |
|
| temperature is less than 40°C (104°F). | |
|
| If the grills are not blocked and the | |
|
| problem persists, contact Technical | |
|
| Support for assistance. | |
|
|
| |
x Alarms | The UPS detects that the input utility | If this occurs in a running system, the | |
| voltage is above the maximum | system will immediately transition to | |
Input AC Over | |||
operating range of about 277 v | Battery mode until valid utility returns. If | ||
Voltage | |||
(288 v | this occurs before a system has | ||
| |||
|
| entered an online state, its startup | |
|
| sequence will not complete, and the | |
|
| system will shut down until valid utility | |
|
| returns. | |
|
| If the condition persists, contact an | |
|
| electrician. | |
|
|
| |
x Alarms | The UPS detects that the input utility | If this occurs in a running system, the | |
| voltage is below the minimum operating | system will immediately transition to | |
Input AC Under | |||
range of about 172 v | Battery mode until valid utility returns. If | ||
Voltage | |||
(160 v + hysteresis). | this occurs before a system has | ||
| |||
|
| entered an online state, its startup | |
|
| sequence will not complete, and the | |
|
| system will shut down until valid utility | |
|
| returns. | |
|
| If the condition persists, contact an | |
|
| electrician. | |
|
|
| |
x Alarms | The UPS detects that the input | If this occurs in a running system, the | |
| frequency has a greater deviation than | system will regulate output frequency to | |
Input Under Or | |||
± 5 Hz from the nominal window of | its nominal 50 or 60 Hz. If this occurs | ||
Over Frequency | |||
operation. | before a system has entered an online | ||
| |||
|
| state, its startup sequence will not | |
|
| complete, and the system will shut | |
|
| down until valid utility returns. | |
|
| If the condition persists, contact an | |
|
| electrician. | |
|
|
| |
|
| continued |
HP Uninterruptible Power System R12000 XR Models User Guide |