LCD Configuration and Status

Matching the Utility Voltage

Use configuration parameters to select the UPS voltage range (see Table 3-1).

If the utility voltage is within this range, the UPS supplies utility power to the output receptacles.

If the utility voltage is outside this range, the UPS supplies battery power to the output receptacles.

If the utility voltage frequently varies outside the operating range, update the UPS configuration to match.

NOTE: When you set the voltage through the LCD panel (as described in the “Setting the Voltage” section of this chapter), you are setting the UPS output voltage

Table 3-1: Voltage Ranges (VAC)

Nominal Utility

Normal Utility

UPS Output

Voltage Level

Voltage Range

Voltage

 

 

 

200

166-240

200

 

 

 

208

166-248

208

 

 

 

220

176-264

220

 

 

 

230 (default)

184-276

230

 

 

 

240

192-288

240

 

 

 

To update the configuration:

1.Have a licensed electrician measure your utility voltage.

2.Use Table 3-1to identify the operating range that most closely matches your nominal utility voltage level.

3.Update the UPS output voltage as required. Refer to the section, “Setting the Voltage,” in this chapter for more information.

3-2

HP Uninterruptible Power System R12000 XR Models User Guide