LCD Configuration and Status
Matching the Utility Voltage
Use configuration parameters to select the UPS voltage range (see Table
•If the utility voltage is within this range, the UPS supplies utility power to the output receptacles.
•If the utility voltage is outside this range, the UPS supplies battery power to the output receptacles.
•If the utility voltage frequently varies outside the operating range, update the UPS configuration to match.
NOTE: When you set the voltage through the LCD panel (as described in the “Setting the Voltage” section of this chapter), you are setting the UPS output voltage
Table
Nominal Utility | Normal Utility | UPS Output |
Voltage Level | Voltage Range | Voltage |
|
|
|
200 | 200 | |
|
|
|
208 | 208 | |
|
|
|
220 | 220 | |
|
|
|
230 (default) | 230 | |
|
|
|
240 | 240 | |
|
|
|
To update the configuration:
1.Have a licensed electrician measure your utility voltage.
2.Use Table
3.Update the UPS output voltage as required. Refer to the section, “Setting the Voltage,” in this chapter for more information.
HP Uninterruptible Power System R12000 XR Models User Guide |