Troubleshooting

Table 5-3: Troubleshooting problems after UPS startup continued

Symptom

Possible Cause

Suggested Action

UPS frequently switches

The utility voltage is frequently

Update the configuration.

between utility and battery

outside the UPS operating

 

power.

range.

 

 

 

 

Utility LED and Redundant

UPS is on utility.

The UPS is operating

LED are lit.

 

normally.

 

 

The system is configured to

 

 

run in Redundant mode and is

 

 

operating within normal load

 

 

limits.

 

 

 

Audible alarm sounds.

UPS is on utility.

Redundant mode is not

Utility LED and Alarm LED are

 

available and the Loss of

 

Redundancy alarm is present.

lit.

 

 

Reduce the load and verify

 

 

 

 

that no other alarms are

 

 

present.

 

 

 

Utility LED is lit.

UPS is on utility.

No action is required. The

 

 

UPS is operating normally.

 

 

The system is configured to

 

 

run in Nonredundant mode

 

 

and is supporting between a

 

 

9 KVA and 12 KVA load.

 

 

 