Troubleshooting
Table
LCD Display | Possible Cause | Suggested Action | |
|
|
| |
x Alarms | The UPS triggers an alarm if the | Ensure that unit grills are not blocked | |
| ambient temperature inside the | and fans are operational. Correct any | |
Ambient Over | |||
detecting electronics module exceeds | environmental conditions that may be | ||
Temperature | |||
the preset threshold of 80°C (176°F). | causing the condition. Verify that the | ||
| |||
| Other than the alarm, no UPS action is | ambient temperature is less than 40°C | |
| currently associated with this condition. | (104°F). | |
|
| Contact Technical Support for | |
|
| assistance. | |
|
|
| |
x Alarms | Batteries are depleted beyond their | This is a normal operation. The UPS | |
| lower limits due to the UPS being on | will restart when utility power is | |
Automatic | |||
battery for an extended period. The | restored. | ||
Shutdown Pending | |||
load has been disengaged and the |
| ||
|
| ||
| system has entered the |
| |
| powerdown mode. |
| |
|
|
|
x Alarms | This alarm is triggered by the one of | |
| the following events: | |
Batteries | ||
| ||
Disconnected | • The UPS detects that at least one | |
| battery is installed incorrectly. | |
| • Not enough battery modules are | |
| installed to support the current | |
| load levels. |
Remove bezels and check that each battery module is firmly seated in its slot. Verify that the load does not exceed 12 kW.
Contact Technical Support for assistance.
x Alarms | At least one electronics module detects | Switch to Maintenance Bypass mode, | |
| that battery voltage is abnormally high | and contact Technical Support for | |
Battery DC Over | |||
while operating in Battery mode. | assistance. | ||
Voltage | |||
|
| ||
|
|
| |
x Alarms | The UPS detects that the current | This is a normal operation. The UPS | |
| battery voltage level has dropped | will begin the shutdown process. | |
Battery Low | |||
below the preset threshold configured |
| ||
|
| ||
| in the EEPROM for this alarm. This is |
| |
| to be expected when operating in |
| |
| Battery mode and when the batteries |
| |
| discharge. |
| |
|
|
|
xAlarms
Battery n Needs
Service
The UPS detects a battery fuse failure | Contact Technical Support for |
or an automated battery test failure. An | assistance. |
automated battery test failure is |
|
reported when battery voltage is less |
|
than 1.8 volts per cell during the first |
|
75 seconds of unscheduled Battery |
|
mode operation. |
|
The variable n indicates the slot in |
|
which the faulted battery module is |
|
installed. (For example, slot 1 is the |
|
uppermost bay of the |
|
slots.) |
|
continued
HP Uninterruptible Power System R12000 XR Models User Guide |