Troubleshooting
Problems During Startup
If problems occur when starting the UPS, refer to Table
Table
Symptom | Possible Cause | Suggested Action |
UPS will not start. There is no utility power.
Unit is hardwired. Contact a qualified electrician to check power at the utility receptacle.
| Batteries are disconnected. | Install the battery trays. If the |
|
| batteries are installed, remove and |
|
| then reinsert the electronics modules. |
|
|
|
| REPO: Audible alarm sounds | Ensure that the REPO switch is in the |
| and Alarm LED is lit. | proper position (open) and utility is |
|
| present. Press the On button. |
|
|
|
Problems After Startup
If problems occur after starting the UPS, refer to Table
Table
Symptom | Possible Cause | Suggested Action |
Audible alarm sounds. | An alarm condition exists. | Scroll through the LCD menu for |
Alarm LED is lit. |
| system alarms to determine the |
| cause. | |
|
| |
|
|
|
Bypass LED is flashing. | Automatic Bypass mode is not | Scroll through the LCD menu for |
| available. | system alarms to determine the |
|
| cause. |
|
| Manual Bypass is not |
|
| recommended during this |
|
| condition. |
|
|
|
Utility LED is flashing slowly, | Utility power is within | Press the On button to assume |
and all other LEDs are off. | acceptable range. | the load. |
| The UPS is operating normally |
|
| and is in Standby mode. |
|
|
|
|
Utility LED is flashing rapidly. | The full UPS or an electronics |
| module is in the process of |
| starting up. |
Wait for continuous Utility or Battery LED light, or slowly flashing Utility LED.
continued
HP Uninterruptible Power System R12000 XR Models User Guide |