![](/images/backgrounds/287203/hp-r12000-xr-users-manual-54839951x1.png)
Troubleshooting
Table
LCD Display | Possible Cause | Suggested Action | |
x Alarms | The UPS detects that the current load | Reduce the load level to clear the | |
| has exceeded 120% of the maximum | alarm. If the alarm persists after load | |
Level 4 Overload – | |||
capacity available, which means it is | reduction, see the LCD panel to | ||
Phase A | |||
operating in Nonredundant mode. | determine which electronics module is | ||
| |||
| The UPS will transfer to Bypass mode | reporting overload. | |
|
| ||
| within one second and remain in that | Contact Technical Support for | |
| mode due to the excessive overload | assistance. | |
| condition. |
| |
|
|
| |
x Alarms | The UPS detects that the current load | If redundant operation is desired, | |
| level has exceeded the maximum safe | reduce the load until the alarm clears. | |
Loss of | |||
load level limits that would provide |
| ||
Redundancy |
| ||
redundancy protection to the |
| ||
|
| ||
| electronics modules. |
| |
| The system will continue to operate, |
| |
| but will no longer be in Redundant |
| |
| mode. The load could be at risk if an |
| |
| electronics module fails. |
| |
|
|
| |
x Alarms | The UPS detects that its electronics | Switch to Maintenance Bypass mode, | |
| modules are having trouble | and restart the system. | |
Loss of | |||
synchronizing with the input utility | Contact Technical Support for | ||
| |||
| source. The most likely cause is a poor | ||
| assistance. | ||
| utility source supplying the UPS. | ||
|
| ||
|
|
| |
x Alarms | While on battery, the UPS detects that | This is a normal operation. | |
| the battery voltage level has dropped |
| |
Low Battery |
| ||
below the lowest preset threshold |
| ||
Shutdown |
| ||
value. The UPS will be shut down. |
| ||
|
| ||
| This normal alarm condition occurs at |
| |
| the end of a battery discharge cycle. |
| |
| The threshold represents the lowest |
| |
| allowable battery discharge level for the |
| |
| batteries before they can no longer |
| |
| safely support the load. Once valid |
| |
| utility returns, the UPS will assume the |
| |
| load after a minimum charge level has |
| |
| been restored to the batteries, and it |
| |
| will begin a complete battery recharge |
| |
| cycle. |
| |
|
|
| |
x Alarms | The UPS detects an EEPROM | Check the website (www.hp.com) for | |
| Checksum Failure in the electronics | Flash upgrades. | |
module or supervisory board. This | Contact Technical Support for | ||
Memory | |||
condition must be resolved before the | |||
Checksum Fail | assistance. | ||
UPS can complete its initialization and | |||
|
| ||
| start successfully. |
| |
| This alarm is most common after a |
| |
| flash upgrade that requires an |
| |
| EEPROM upgrade for the new |
| |
| embedded software to function |
| |
| correctly. The upgrade documentation |
| |
| will describe this condition. |
| |
|
|
| |
|
| continued |
HP Uninterruptible Power System R12000 XR Models User Guide |