Step 6 Detailed Setup (Continued)

6-5 ALARM SETUP screen (Continued)

 

 

Item

Content

 

Default value

Input Pin

Select the pin no. of the alarm port to set.

1

 

* Following settings are to

[Variable: 1~4]

 

 

 

be performed for each pin.

 

 

 

 

 

 

 

 

 

 

 

 

Trigger

Select the polarity of the alarm input signal.

Disabled

 

 

 

Input signal is invalid when setting to Disable.

 

 

 

 

 

 

[Variable: Low, High, Disabled]

 

 

 

 

 

 

 

 

 

 

 

Trigger Duration

Set the length of input signal to assume as an alarm.

100ms

 

 

 

[Variable: 50ms, 100ms, 200ms, 300ms, 400ms, 500ms]

 

 

 

 

 

 

 

 

 

 

 

Recording Duration

CF recording duration triggered by alarm is set. Duration

 

 

 

 

 

 

 

 

 

 

before the alarm and duration after the alarm are set.

 

 

 

 

 

 

The maximum time for CF recording triggered by one alarm

 

 

 

 

 

 

is 30 seconds. (Set so that the total time of Before Trigger

 

 

 

 

 

 

and After Trigger is 30 seconds or less.)

 

 

 

 

 

 

0 cannot be set for both Before Trigger and After Trigger.

 

 

 

 

 

 

* For CF recording, set JPEG in the ENCODE PARAMETERS

 

 

 

 

 

 

screen to “Video In 1” or “Video In 2”. (See page 32)

 

 

 

 

 

 

* Recording will be made before and after for about 1 sec-

 

 

 

 

 

 

ond even when setting to 0s.

 

 

 

 

 

 

 

 

 

 

 

 

Before Trigger

Set the length of time of CF recording before alarm input.

10s

 

 

 

[Variable: 0s, 5s, 10s, 15s, 20s] (Unit: sec)

 

 

 

 

 

 

 

 

 

 

 

 

After Trigger

Set the length of time of CF recording after alarm input.

20s

 

 

 

[Variable: 0s, 5s, 10s, 15s, 20s] (Unit: sec)

 

 

 

 

 

 

 

 

 

 

 

Comment

Input characters must be alphanumerical characters

dm-nc40

 

 

 

with a maximum of 64 characters.

 

 

 

 

 

 

 

 

 

 

Send To

 

 

 

 

 

 

 

 

 

 

 

 

Item

Content

 

Default value

 

 

 

 

 

 

 

IP Address

Set the address to send the alarm information.

 

Blank

 

 

 

Up to 2 destination addresses can be specified.

 

 

 

 

 

 

 

 

 

 

Port

Set the port number to send the alarm information.

10000

 

 

 

The maximum value is 65535.

 

 

 

 

 

 

 

 

 

 

Data

Set the sending data. Up to 64 characters can be entered.

 

data

 

 

 

 

 

 

 

Protocol

Set the transmission protocol:

 

TCP

 

 

 

TCP: Alarm information is sent by TCP.

 

 

 

 

 

 

Character string entered in Data will be sent to the

 

 

 

 

 

 

set port no.

 

 

 

 

 

 

Some custom application software may be required

 

 

 

 

 

 

to receive the alarm information by TCP.

 

 

 

 

 

 

API: Select when sending the alarm information to

 

 

 

 

 

 

monitor side DM-NC40 for automatic connection.

 

 

 

 

 

 

Port is set to “-----” (default) and Data is set to

 

 

 

 

 

 

“Disable”.

 

 

 

 

 

 

 

 

 

 

* When clicking

with Comment and Data left blank, an underscore (_) will be inserted automatically.

38