6. HARVEST

The harvest valve(s) remains open and the refrigerant gas warms the evaporator. This causes the cubes to slide, as a sheet, off the evaporator and into the storage bin.

The sliding sheet of cubes swings the water curtain out, opening the bin switch. This momentary opening and closing of the bin switch terminates the Harvest Cycle and returns the ice machine to the Freeze Cycle (steps 3-4).

The air compressor (when used) remains energized throughout the entire harvest cycle. The air compressor will automatically energize after 60 seconds when the harvest cycle time exceeded 75 seconds in the previous cycle.

L1

 

 

 

 

L2 or N

Ground

 

 

 

 

 

 

 

Water Valve

(99)

 

 

 

 

 

 

 

(20)

(21)

 

(89)

(55)

 

 

(61)

(22)

 

 

High

 

 

 

Control Board

 

Harvest Valve

 

 

Pressure

 

 

 

(2)

 

 

(88)

Cutout

(60)

(77)

 

(6)

 

 

 

(80)

 

 

 

(5)

 

Dump Valve

(75)

 

 

(1)

 

(76)

 

 

(7)

 

(81)

 

 

 

(4)

(57)

Water Pump

 

 

 

 

(98)

 

 

 

 

 

 

 

(42)

Trans.

 

 

 

Fuse (7a)

(58)

Terminates at

 

 

 

Pin Connection

 

 

 

 

 

(59)

 

 

 

L2

 

Contactor Coil

 

 

 

(25)

 

(56)

 

 

 

 

(26)

Air Compressor

 

 

 

 

 

Ice Thickness

 

(9)

 

 

(74)

Probe

 

(8)

 

Water Level Probe

 

 

 

Bin Switch

 

Low DC

 

(6)

 

 

 

 

 

 

 

Voltage

 

 

Clean

 

 

Plug

 

(1)

 

 

 

OFF

 

 

 

 

 

 

 

 

(2)

ICE

 

 

(Red)

 

 

 

 

 

 

 

 

 

Compressor

 

 

Contactor

Overload

(Yellow)

(46)

Run Capacitor

 

 

 

(50)

Contacts

 

 

 

 

(Black)

 

 

 

 

(45)

L1

 

 

 

 

(51)

(85)

(86)

 

PTCR

 

Fan Motor

 

Fan Cycle

 

 

 

 

 

 

Control

 

 

 

 

 

Run Capacitor

 

 

 

SV3137-7

Table 6-6. Self-Contained Models

 

 

 

 

 

 

 

6. Harvest (Until Bin Switch Activation)

 

 

Toggle Switch

 

ICE

Bin Switch

 

Closed

Control Board Relays

 

 

#1

Water Pump

 

OFF

#2

Harvest Valve (Left)

 

ON

#3

Harvest Valve (Right)

 

ON (When Used)

#4

Air Compressor

 

ON (When Used)

#5

Water Inlet Valve

 

OFF

#6

Water Dump Valve

 

OFF

#7

Contactor Coil

 

Closed / ON

#7A

Compressor

 

ON

#7B

Condenser Fan Motor

 

OFF; May Cycle ON

Safety Controls (Which could stop ice machine operation)

 

 

 

High Pressure Cut-Out

 

Closed

 

Main Fuse (On Control Board)

 

Closed

Part Number 80-1634-3

6-7

Page 45