Section 6

Electrical System

 

 

2.REFRIGERATION SYSTEM START-UP

The compressor starts after the 45- second water purge, and it remains on throughout the Freeze and Harvest cycles.

The water fill valve is energized at the same time as the compressor.

The harvest valve(s) remains on for the first 5 seconds of the initial compressor start-up and then shuts off.

At the same time the compressor starts, the condenser fan motor (air- cooled models) is supplied with power throughout the entire freeze and harvest sequences.

The fan motor is wired through a fan cycle pressure control, and may cycle on and off. (The compressor and the condenser fan motor are wired through the contactor. Any time the contactor coil is energized, the compressor and fan motor are supplied with power.)

L1

 

 

 

 

L2 or N

Ground

 

 

 

 

 

 

 

Water Valve

(99)

 

 

 

 

 

 

 

(20)

(21)

 

(89)

(55)

 

 

(61)

(22)

 

 

High

 

 

 

Control Board

 

Harvest Valve

 

 

Pressure

 

 

 

(2)

 

 

(88)

Cutout

(60)

(77)

 

(6)

 

 

 

(80)

 

 

 

(5)

 

Dump Valve

(75)

 

 

(1)

 

(76)

 

 

(7)

 

(81)

 

 

 

(4)

(57)

Water Pump

 

 

 

 

(98)

 

 

 

 

 

 

 

(42)

Trans.

 

 

 

Fuse (7a)

(58)

Terminates at

 

 

 

Pin Connection

 

 

 

 

 

 

(59)

 

 

 

L2

 

 

Contactor Coil

 

 

 

(25)

 

 

(56)

 

 

 

 

(26)

 

Air Compressor

 

 

 

 

 

 

Ice Thickness

 

(9)

 

 

 

(74)

Probe

 

(8)

 

 

Water Level Probe

 

 

 

Bin Switch

 

Low DC

 

(6)

 

 

 

 

 

 

 

 

 

Voltage

 

(1)

 

Clean

 

 

Plug

 

 

 

 

 

 

 

 

OFF

 

 

 

 

(2)

 

ICE

 

 

(Red)

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

Run Capacitor

 

 

(Yellow)

(46)

Contactor

Overload

 

 

 

 

 

(50)

Contacts (Black)

 

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

 

 

(45)

(51)

(85)

(86)

 

 

PTCR

 

Fan Motor

 

Fan Cycle

 

 

 

 

 

 

 

Control

 

 

 

 

Run Capacitor

SV3137-4

 

Self-Contained — Refrigeration System Start-Up

Table 6-2. Self-Contained Models

 

 

 

 

 

2. Refrigeration System Start Up (5 Seconds)

 

Toggle Switch

ICE

Bin Switch

Closed

Control Board Relays

 

#1

Water Pump

OFF

#2

Harvest Valve (Left)

ON

#3

Harvest Valve (Right)

ON (When Used)

#4

Air Compressor

ON (When Used)

#5

Water Inlet Valve

ON

#6

Water Dump Valve

OFF

#7

Contactor Coil

Closed / ON

#7A

Compressor

ON

#7B

Condenser Fan Motor

OFF

Safety Controls (Which could stop ice machine operation)

 

 

High Pressure Cut-Out

Closed

 

Main Fuse (On Control Board)

Closed

Part Number 80-1634-3

6-3

Page 41