Manitowoc Ice S1800 service manual Harvest Sequence, Water Purge

Models: S1800

1 100
Download 100 pages 24.15 Kb
Page 44
Image 44

Electrical System

Section 6

 

 

Harvest Sequence

5. WATER PURGE

The harvest valve(s) opens at the beginning of the water purge to divert hot refrigerant gas into the evaporator.

The water pump continues to run, and the water dump valve energizes for 45 seconds to purge the water in the sump trough. The water fill valve energizes and de-energizes strictly by time. The water fill valve energizes for the last 15 seconds of the 45- second water purge.

After the 45 second water purge, the water fill valve, water pump and dump valve de-energize. (Refer to “Water Purge Adjustment” for details.)

The air compressor (when used) will energize after 35 seconds.

L1

 

 

 

L2 or N

Ground

 

 

Water Valve

(99)

 

 

(20)

(89)

(55)

(21)

 

(61)

(22)

 

High

 

 

Control Board

 

Harvest Valve

 

Pressure

 

 

(2)

 

 

(88) Cutout

(60)

(77)

 

(6)

 

 

(80)

 

 

(5)

 

Dump Valve

(75)

 

(1)

 

(76)

 

 

(7)

 

(81)

 

 

(4)

(57)

Water Pump

 

 

 

(98)

 

 

 

 

 

(42)

Trans.

(58)

 

 

 

Fuse (7a)

Terminates at

 

 

 

 

 

 

 

Pin Connection

 

 

 

 

 

 

(59)

 

 

 

L2

 

Contactor Coil

 

 

 

(25)

 

(56)

 

 

 

 

(26)

Air Compressor

 

 

 

 

 

Ice Thickness

 

(9)

 

 

(74)

Probe

 

(8)

 

Water Level Probe

 

 

 

Bin Switch

 

Low DC

 

(6)

 

 

 

 

 

 

 

Voltage

 

 

Clean

 

 

Plug

 

(1)

 

 

 

OFF

 

 

 

 

 

 

 

 

(2)

ICE

 

 

(Red)

 

 

 

 

 

 

 

 

 

Compressor

 

Run Capacitor

Contactor

Overload

(Yellow)

(46)

 

 

 

(50)

Contacts

 

 

 

 

(Black)

 

 

 

 

(45)

L1

 

 

 

 

(51)

(85)

(86)

 

PTCR

 

Fan Motor

 

Fan Cycle

 

 

 

 

 

 

Control

 

 

 

Run Capacitor

SV3137-6

 

 

 

Self-Contained — Water Purge

Table 6-5. Self-Contained Models

 

 

 

 

 

 

 

 

5. Water Purge (45 Seconds)

Toggle Switch

 

ICE

Bin Switch

 

Closed

Control Board Relays

 

 

#1

Water Pump

 

ON

#2

Harvest Valve (Left)

 

ON

#3

Harvest Valve (Right)

 

ON (When Used)

#4

Air Compressor

 

ON; after 35 seconds

#5

Water Inlet Valve

 

30 seconds OFF,

 

15 seconds ON

 

 

 

#6

Water Dump Valve

 

ON

#7

Contactor Coil

 

Closed / ON

#7A

Compressor

 

ON

#7B

Condenser Fan Motor

 

OFF; May Cycle ON

Safety Controls (Which could stop ice machine operation)

 

 

High Pressure Cut-Out

 

Closed

 

Main Fuse (On Control Board)

 

Closed

6-6

Part Number 80-1634-3

Page 44
Image 44
Manitowoc Ice S1800 service manual Harvest Sequence, Water Purge