Manitowoc Ice S1800 service manual Section Electrical System, Energized Parts Charts

Models: S1800

1 100
Download 100 pages 24.15 Kb
Page 39
Image 39

Section 6

Electrical System

 

 

Section 6

Electrical System

Energized Parts Charts

SELF-CONTAINED WATER-COOLED MODELS

 

 

 

Control Board Relays

 

 

Contactor

 

Ice Making

1

2

3

4

5

6

7

7A

7B

Length

Sequence Of

 

Harvest

Harvest

 

Water

 

 

 

Cond.

Water

Air

Dump

Contactor

 

Of Time

Operation

Valve

Valve

Inlet

Comp.

Fan

Pump

Comp.*

Valve

Coil

 

 

(Left)

(Right)*

Valve

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

35 sec.

 

 

 

 

 

 

START-UP 1

 

 

On

Off

 

 

 

 

 

 

On

On

(when

 

Off

On

Off

Off

Off

45 Seconds

1. Water Purge

 

 

 

used)

10 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On

 

 

 

 

 

 

2. Refrigeration

Off

On

Off

Off

On

Off

On

On

Off

5 Seconds

System Start-Up

 

 

 

 

 

 

 

 

 

 

FREEZE

 

 

 

 

May

 

 

 

 

Initial Start-Up

 

 

 

 

Cycle

 

 

 

May Cycle

is 60 Seconds

SEQUENCE

Off

Off

Off

Off

Off

On

On

On/Off

On/Off

30 Seconds

3. Pre-Chill

 

 

 

 

 

 

 

 

 

 

 

during

 

 

 

 

thereafter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the first

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45 sec.

 

 

 

 

Until 10 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cycles

 

 

 

May Cycle

water contact

4. Freeze

On

Off

Off

Off

Off

On

On

with ice

Off, then

On/Off

 

 

 

 

 

 

 

 

thickness

 

 

 

 

 

On one

 

 

 

 

 

 

 

 

 

 

 

 

 

probe

 

 

 

 

 

more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

time

 

 

 

 

 

HARVEST

 

 

 

 

30 sec.

 

 

 

 

 

 

 

 

On; after

Off,

 

 

 

May Cycle

Factory-set at

SEQUENCE

On

On

On

On

On

On

35 sec.

15 sec.

On/Off

45 Seconds

5. Water Purge

 

 

 

 

 

 

 

 

 

 

On

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6. Harvest

Off

On

On

On

Off

Off

On

On

May Cycle

Bin switch

On/Off

activation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Until bin

7. AUTOMATIC

Off

Off

Off

Off

Off

Off

Off

Off

Off

switch

SHUT-OFF

re-closes &

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 min. delay

1.Initial Start-Up or Start-Up After Automatic Shut-Off * Not Used on all Models

Condenser Fan Motor

The fan motor is wired through a fan cycle pressure control, therefore, it may cycle on and off.

Harvest Water Purge

The circuit board has an adjustable water purge in the harvest cycle. This permits a 0 or 45 second purge cycle.

Auto Shut-Off

The ice machine remains off for 3 minutes before it can automatically restart. The ice machine restarts (steps 1-2) immediately after the delay period, if the bin switch re-closes prior to 3 minutes.

Safety Timers

The control board has the following non-adjustable safety timers:

The ice machine is locked into the freeze cycle for 6 minutes, before a harvest sequence can be initiated. The freeze lock is bypassed when the toggle switch is moved from the OFF to ICE position on the first cycle only.

The maximum freeze time is 60 minutes, at which time the control board automatically initiates a harvest sequence (steps 5-6).

The maximum harvest time is 3-1/2 minutes, at which time the control board automatically terminates the harvest sequence. If the bin switch is open, the ice machine will go to automatic shut-off (step 7). If the bin switch is closed, the ice machine will go to the freeze sequence (steps 3-4).

Part Number 80-1634-3

6-1

Page 39
Image 39
Manitowoc Ice S1800 service manual Section Electrical System, Energized Parts Charts, SELF-CONTAINED WATER-COOLED Models