Refrigeration System

Section 7

 

 

Freeze Cycle Suction Pressure High Checklist

 

 

Possible Cause

Check/Correct

Improper installation

See “Installation/Visual Inspection Checklist”

Discharge pressure

Discharge pressure is too high, and is affecting low side

 

(See “Freeze Cycle Discharge Pressure High Checklist” )

Improper refrigerant charge

Overcharged

 

Wrong type of refrigerant

Other

Non-Manitowoc components in system

 

Harvest valve stuck open

 

TXV flooding (check bulb mounting)

 

Defective compressor

Freeze Cycle Suction Pressure Low Checklist

Possible Cause

Check/Correct

Improper installation

See “Installation/Visual Inspection Checklist”

Discharge pressure

Discharge pressure is too low, and is affecting low side

 

(See “Freeze Cycle Discharge Pressure Low Checklist”)

Improper refrigerant charge

Undercharged

 

Wrong type of refrigerant

Other

Non-Manitowoc components in system

 

Improper water supply over evaporator (See “Water System Checklist” )

 

Loss of heat transfer from tubing on back side of evaporator

 

Restricted/plugged liquid line drier

 

Restricted/plugged tubing in suction side of refrigeration system

 

TXV starving

NOTE: Do not limit your diagnosis to only the items listed in the checklists.