Manitowoc Ice S1800 SELF-CONTAINED Models, Initial Start-Up or Start-Up After Automatic Shut-Off

Models: S1800

1 100
Download 100 pages 24.15 Kb
Page 40
Image 40

Electrical System

Section 6

 

 

Wiring Diagram Sequence of Operation

SELF-CONTAINED MODELS

Initial Start-Up or Start-Up After Automatic Shut-Off

1. WATER PURGE

Before the compressor starts, the water pump and water dump solenoid are energized for 45 seconds to purge old water from the ice machine. This ensures that the ice-making cycle starts with fresh water.

The harvest valve(s) is also energized during the water purge. In the case of an initial refrigeration start-up or auto shut-off, it stays on for an additional

5 seconds (50 seconds total).

The air compressor energizes for the last 10 seconds of the cycle.

L1

 

 

 

 

L2 or N

Ground

 

 

 

Water Valve

 

 

 

 

 

 

(89)

(55)

(20)

(21)

(99)

(61)

 

(22)

High

 

 

 

Control Board

 

Harvest Valve

 

Pressure

 

 

(2)

 

(77)

 

 

(88) Cutout

(6)

(60)

 

(80)

 

 

 

 

 

(5)

 

Dump Valve

(75)

 

(1)

 

 

 

 

 

(7)

 

(76)

(81)

 

 

(4)

(57)

Water Pump

 

 

 

(98)

 

 

 

 

 

 

 

(42)

Trans.

(58)

 

 

 

 

Fuse (7a)

 

Terminates at

 

 

 

 

 

 

 

 

(59)

Pin Connection

 

 

 

 

 

 

 

 

L2

Contactor Coil

 

(25)(56)

 

 

 

(26)

Air Compressor

 

 

 

 

Ice Thickness

(9)

 

 

(74)

Probe

(8)

 

Water Level Probe

 

 

Bin Switch

Low DC

 

(6)

 

 

 

 

 

Voltage

 

(1)

Clean

 

Plug

 

 

 

 

 

OFF

 

 

 

 

ICE

 

 

(Red)

(2)

 

 

 

Compressor

 

 

Contactor

Overload

(Yellow)

(46)

Run Capacitor

 

 

(50)

Contacts

(Black)

 

 

L1

 

 

(45)

 

 

 

(51)

(85)

(86)

PTCR

 

Fan Motor

Fan Cycle

Control

Run Capacitor

SV3137-2

 

 

Self-Contained — Water Purge

Table 6-1. Self-Contained Models

 

 

 

 

 

 

 

 

1. Water Purge (45 Seconds)

Toggle Switch

 

ICE

Bin Switch

 

Closed

Control Board Relays

 

 

#1

Water Pump

 

ON

#2

Harvest Valve (Left)

 

ON

#3

Harvest Valve (Right)

 

ON (When Used)

#4

Air Compressor

 

35 sec. OFF / 10 sec. ON

#5

Water Inlet Valve

 

OFF

#6

Water Dump Valve

 

ON

#7

Contactor Coil

 

Open / OFF

#7A

Compressor

 

OFF

#7B

Condenser Fan Motor

 

OFF

Safety Controls (Which could stop ice machine operation)

 

 

High Pressure Cut-Out

 

Closed

 

Main Fuse (On Control Board)

 

Closed

6-2

Part Number 80-1634-3

Page 40
Image 40
Manitowoc Ice S1800 SELF-CONTAINED Models, Initial Start-Up or Start-Up After Automatic Shut-Off, Water Purge