Section 7

Refrigeration System

 

 

Safety Limit #2

Refer to page 7-11 for safety limit operation.

Harvest time exceeds 3.5 minutes for 500 consecutive harvest cycles.

Possible Cause

Check/Correct

Improper installation

See “Installation/Visual Inspection Checklist”

Water system

Water area (evaporator) dirty

 

Dirty/defective water dump valve

 

Vent tube not installed on water outlet drain

 

Water freezing behind evaporator

 

Plastic extrusions and gaskets not securely mounted to the

 

evaporator

 

Low water pressure [20 psi (138 kPa) min.]

 

Loss of water from sump area

 

Clogged water distribution tube

 

Dirty/defective water fill valve

 

Defective water pump

Electrical system

Ice thickness probe out of adjustment

 

Ice thickness probe dirty

 

Bin switch defective

 

Premature harvest

Refrigeration system

Non-Manitowoc components

 

Water regulating valve dirty/defective

 

Improper refrigerant charge

 

Defective harvest valve

 

TXV flooding (check bulb mounting)

SAFETY LIMIT NOTES

Because there are many possible external problems, do not limit your diagnosis to only the items listed in this chart.

A continuous run of 100 harvests automatically erases the safety limit code.

The control board will store and indicate only one safety limit – the last one exceeded.

If the toggle switch is moved to the OFF position and then back to the ICE position prior to reaching the 100-harvest point, the last safety limit exceeded will be indicated.

If a Safety Limit light did not flash prior to the ice machine restarting, then the ice machine did not stop because it exceeded a safety limit.

Part Number 80-1634-3

7-11

Page 77
Image 77