Power supply installation Standard 1.0
44 CallPilot
DC wire gauge tables
Introduction
The tables in this section specify the DC power feed wire requirements.

Cabinet and module DC feed recommended wire gauge

specifications

Notes:
1. Cabinet and module ground wire specification is #10 AWG insulated
green safety ground wire.
2. Cabinet conduit can be 1.91 cm (0.75 in.) or 3.18 cm (1.25 in.), and must
be insulated from cabinet ground.
Length #10 AWG #8 AWG #6 AWG
Junction
box #4
AWG
Junction
box #4
AWG
030 m (100 ft) yes yes yes yes yes
045 m (150 ft) no yes yes yes yes
075 m (250 ft)nonoyesyesyes
0135 m (450 ft) no no no yes yes
0210 m (700 ft) no no no no yes
Over 210 m (700 ft) no no no no no