Pressure Systems 98RK-1 Command c- Sub-command Index 03 Clear Stream, “c 03 st”, Packet, Example

Models: 98RK-1

1 153
Download 153 pages 51.42 Kb
Page 69
Image 69
Command 'c'— Sub-command Index 03: Clear Stream

Pressure Systems, Inc.

98RK-1 & 9816 User’s Manual©

 

 

Command 'c'— Sub-command Index 03: Clear Stream

This sub-command is used to “undefine” any previously configured host stream in a module, one at a time, or all together. The sub-command’s format is:

Command

c 03 st

 

‘c’ is the command letter.

03’ is the sub-commandindex (ii) for Clear Stream.

st’ is the stream id digit (1, 2, or 3, or 0=all streams).

NOTE: all parameters are separated by a space.

Response A

‘A’ is the acknowledge letter.

Autonomous none generated

Packet

Description: This sub-command clears (un-defines) the particular specified host stream (st=1- 3); or un-defines “all configured” host streams with a single command (st=0). Once cleared, a stream must be reconfigured before it can be started.

Example:

Stop all the streams configured above. Then clear (undefine) only stream 3 and then resume the remaining defined streams 1 and 2:

c 02 0” “c 03 3” “c 01 0

Read response:

"A"