User’s Manual
Model 98RK-1 & Model Rackmount Intelligent Pressure Scanner
August NetScanner System
This User’s Manual is a copyright product of Pressure Systems, Inc
Chapter General Information 1.1 Introduction
Typical NetScanner System Configuration
1.2 Description of the Instruments
1.3.1 Pressure Ranges
1.3 Options
1.3.2 Manifolds and Pressure Connections
1.3.3 Communication Interfaces
98RK-1 Rear Panel
Chapter Installation and Set Up 2.1 Unpacking and Inspection
2.2 Safety Considerations
98RK-1 Scanner Interface Rack chassis
98RK-1 Scanner Interface Rack User’s Manual on CD-ROM
2.3.1 98RK-1 Chassis Connections with 9816 Scanners
2.3 Connections and Setup
2.3.2 Connections for External Modules
Typical Hook-up Arrangement Using the 98RK-1 Scanner Interface Rack
Pressure Systems, Inc
98RK-1 & 9816 User’s Manual
Page
2.3.3 Network Communications Hookup
STEP
Initial Network Screen for Windows XP
STEP
STEP
98RK-1 & 9816 User’s Manual
Pressure Systems, Inc
Page
scanners, must be set
To set the PC address Select Use the following TCP/IP address. It is suggested that the IP Address read 200.xxx.yyy.zzz where xxx, yyy, and zzz are unique locations that do not match any other address on the network. Check with your
wait 10 seconds before reconnecting
C\ NUSS\NUSS.EXE
C for instructions on how to create a shortcut icon
NUSS Initial Screen
There are two modules with the same IP address
2.3.4 Pressure Connections
98RK-1 Rear View
Expanded View of Model 9816 Intelligent
Figure 2.3a
Expanded View of 98RK-1 Scanner
2.3.4.2 RUN Mode Inputs
2.3.4.1 Supply Air
2.3.4.3 CAL Mode Inputs
Connection
Pneumatic Connector Assignment 98RK-1
Pressure Scanner Range Input
2.3.4.4 PURGE Mode Inputs
2.3.4.5 LEAK Mode Inputs
2.3.5 Cluster, Rack, and Slot Identification
LED INDICATORS
2.3.4.6 Calibration Manifold Position Detector Circuit
VALVE POSITION
98RK-1 Front Pull-out Tray Diagram Top and Front Views
Typical Depiction of C-R-S Scanner Identification
2.4 Acquiring Data
3.1.1 Introduction
Chapter Programming and Operation 3.1 Commands & Responses
3.1.2 TCP/UDP/IP Protocols
3.1.3.1 General Command Format
3.1.3 Commands
a 1-character command letter c
“cccccc dddd”
3.1.3.2 Command Field
3.1.3.3 Position Field
3.1.3.4 Datum Fields
3.1.3.5 Format Field
3.1.4 Responses
an Acknowledge with Data response, or
3.1.4.1 Interpreting Offset Values Re-zero Calibration Adjustment
3.1.4.2 Interpreting Gain Values Span Calibration Adjustment
CODE
MEANING
3.1.4.3 Interpreting Engineering Units Output
3.1.5 Functional Command Overview
3.1.5.1 Start-up Initialization
3.1.5.2 Module Data Acquisition
3.1.5.3 Calibration Adjustment of Offset/Gain Correction Coefficients
3.1.5.4 Delivery of Acquired Data to Host
3.1.5.5 Network Query and Control Functions
3.1.5.6 Other Functions
3.2 Detailed Command Description Reference
Model 9816 NetScanner System Commands
command id
Power-up Clear
POWER UP CLEAR Command A
Command
‘A’ is the command letter
Response
RESET Command B
Command
Response
Example
CONFIGURE/CONTROL MULTI-POINT CALIBRATION Command C
Command “C ii dddd... ”
‘ 00’ is the sub-command index ii for Configure & Start
Command “C 00 pppp npts ord avg”
NOTE all parameters are separated by a space Response “A”
Example
Configure and start the Multi-Point Calibration function so that it affects only the first four 4 channels of the module. Three 3 pressure calibration points will by supplied when we continue this function later see example for ‘01’ sub-command below. A linear 1st order fit will be used to obtain a new set of offset and gain correction coefficients for these four 4 channels. The maximum average sample count 64 is used to collect each calibration data point, so as to minimize any noise in the data samples. The module’s data acquisition process is altered immediately to collect the increased number of averages
“C 00 F 3 1 64” Read response A
Command C- Sub-command Index 01 Collect Data for a Calibration Point
Command
‘ 01’ is the sub-command index ii for Collect Data
“ C 01 pnt pppp.pppp ”
Example
Read responses separately after each command executed above
“C 01 1 -2.5” “C 01 2 0.0” “C 01 3 5.0”
Command
‘ 02’ is the sub-command index ii for Calculate & Apply
“C 02”
NOTE all parameters are separated by a space
Read responses separately for each command executed above
Example
“C 02” “w08” “w09”
A A A
Command C- Sub-command Index 03 Abort Multi-Point Calibration
Command
‘ 03’ is the sub-command index ii for Abort
“C 03”
READ TRANSDUCER VOLTAGES Command
Command
“Vpppppf”
Response
Example
“V11110”
“V300000”
Response contains data for channels S then P left to right
CALCULATE AND SET GAINS Command Z
Command
“Zpppp vv.vvvv”
Response
Example
Send TCP/IP command to a 9816 module via its open socket to calculate and set gain coefficients for channels 8 through 4. Instruct the module to use 14.8890 psi as the applied pressure instead of each transducer’s full-scale value
“Z00F8 14.8890” Response 1.01289 1.06953 1.03750 0.99704
READ TRANSDUCER A/D COUNTS Command a
Command
“apppppf”
Response
Example
“a11110”
32767.000000 -32700.000000 10.000000
“a300000”
READ HIGH-SPEED DATA Command b
aaaabbbbcccc..rrrr
DEFINE/CONTROL AUTONOMOUS HOST STREAMS Command c
Command
“c ii dddd... ”
NOTE all parameters are separated by a space
first parameter
Command c- Sub-command Index 00 Configure a Host Delivery Stream
Command
“c 00 st ppppp sync per f num”
Response
converts each internal selected acquired datum value from
max.char
Example
Read responses “A” “A” “A”
“c 00 1 000F 0 1 7 0” “c 00 2 00F0 0 2 7 0” “c 00 3 FF00 0 4 7 0”
A A A
Command c- Sub-command Index 01 Start Stream
Command
“c 01 st”
NOTE all parameters are separated by a space
Example
c 01
Command c- Sub-command Index 02 Stop Stream
Command
“c 02 st”
NOTE all parameters are separated by a space
Command c- Sub-command Index 03 Clear Stream
Command
“c 03 st”
NOTE all parameters are separated by a space Response “A”
Command c - Sub-command Index 04 Return Stream Information
Command
‘ 04’ is the sub-command index ii for Return Info
Response “st ppppp sync per f num”
Command c - Sub-command Index 05 Select Data in a Stream
Command
“c 05 st bbbb”
NOTE all parameters are separated by a space
Enable Valve Position Status see next table
Enable DH Temperature Status see bit map below
Enable Pressure EU Data default if never executed
Enable Pressure A/D Counts
Example
Configure stream l to return both status fields, and all Pressure EU data
c 05 1 0013 Read response A
Command c - Sub-command Index 06 Select Protocol for Stream Delivery
Command
“c 06 st pro remport ipaddr”
NOTE all parameters separated by a space
converts each internal selected acquired datum value from
max.char
Example
c 06 0 1 7500 Read response A
CALCULATE AND SET OFFSETS Command h
Command
w command index
“hpppp vv.vvvv”
Example
Send TCP/IP command to a Model 9816 module via its open socket to calculate and set new offset coefficients for channels 16 through
“hF000” Response 0.0010 0.0020 0.0015
READ TEMPERATURE COUNTS Command m
Command
“mpppppf”
Response
“m11110”
Example
32767.000000 -32700.000000 10.000000
READ TEMPERATURE VOLTAGES Command n
Command “ n p ppppf ”
Response
“ dddd dddd ... ”
“n11110”
Example
0.53013 0.541698 0.503633
READ MODULE STATUS Command q
Command
Response
“hhhh ”
IP Address Resolution Method, as hex state
Auto UDP Broadcast@Reset, as hex state
Temperature Status of Each Scanner Transducer, as 16-bit hex bit map
Minimum Temperature Alarm Set Point in degrees C, as decimal
Request model number from any NetScanner System module “q00”
Example
9816
READ HIGH-PRECISION DATA Command r
Command “ r p ppppf ”
Response
“ dddd dddd ... ”
Example
“r11110”
Response contains data for channels 13, 9, 5, and 1 left to right
1.234000 0.989500 1.005390
READ TRANSDUCER TEMPERATURE Command t
Command “tpppppf”
position field
Response
READ INTERNAL COEFFICIENTS Command u
Command
“ufaacc-cc”
Response
Re-zero Cal Adjustment offset term
Span Cal Adjustment gain term
Transducer Coefficient Description
Datum Type
EU Pressure Conversion Scaler default =
Transducer Coefficient Description
Datum Type
Other Coefficients Description
Send TCP/IP command to 9816 module via its connected socket requesting the most recent calibration adjustment’s offset and gain terms cc=00-01, and the adjacent factory-determined transducer coefficients C0 through C4 cc=02-06 for transducer 1 Data requested in ASCII-hex format representing the internal binary floating point format
“N07” error response
Example
u10100-06 Response returned is 3B200A6E
DOWNLOAD INTERNAL COEFFICIENTS Command
Command
converts each datum parameter value ‘ dddd’ from
max.char
Send TCP/IP command to 9816 module i.e., via its connected socket with replacement values for the channel’s offset and gain correction terms loaded into the module’s volatile memory cc = 00-01. Load these into channel # 8s Transducer Coefficient array aa=08
Example
“v00800-01 0.000 1.000” Response returned is A
V01101 6.894757 Response returned is A
SET/DO OPERATING OPTIONS/FUNCTIONS Command w
Command
Update Internal Thermal Coefficients
Set Number of Channels in Module default =16
chart
Disable periodic Thermal Coefficient Update task
Enable periodic Thermal Coefficient Update task
Set Number of A/D Samples to Average . default =
Set Thermal Update Scan Interval per eeee as decimal
Enable Source Air Check default
Disable Source Air Check
Description
Insure in RUN/CAL valve mode
Example
“w1200 ”
“w0C01 ”
NETWORK QUERY UDP/IP Command psi9000
Command
TCP Connect Port default =
IP Address Resolution Method
Example
Query all modules on then network
psi9000
See response above
RE-BOOT MODULE UDP/IP Command psireboot
Command
“psireboot ethadr”
psireboot 12-34-56-78-90-12 Response None
Command
“psirarp ethadr”
Response
Example
Chapter Calibration 4.1 Introduction
CSPAN
Figures 4.1 Pneumatic Diagrams of the Calibration Manifold
scanner
4.2 Re-zero Calibration
4.2.1. Re-zero Calibration Valve Control
4.3 Span Calibration
4.2.2 Re-zero Calibration Summary
Description
TCP/IP Data
4.3.1. Span Calibration Valve Control
Pneumatic Connector Assignment on Rear Input Panel of the 98RK-1
Connection
Pressure Scanner Range Input
4.3.2. Span Calibration Summary
the LOWEST installed pressure range
Description
TCP/IP Data
4.4 Integrated Multi-Point Calibration Adjustment
Description
TCP/IP Data
see Section
4.4.1. Calibration Valve Control
coefficients in transducer non-volatile memory
Description
4.4.2 Multi-Point Calibration Summary
TCP/IP Data
4.6 Line Pressure Precautions
4.5 Coefficient Storage
Chapter Service 5.1 Maintenance
Exploded View of 9816 Calibration Manifold
9816 with Upgraded Purge Block
Component
Section
Table 5.1 Component Cross Reference
5.1.1 Common Maintenance
l is not provided in the maintenance kit
5.1.2 Module Disassembly
PC299 Board
5.1.3
Electronic Circuit Board Replacement
5.1.3.1 PC-206 Amplifier/Multiplexer Board
9816 Calibration Valve Out of its Case Showing PC-206 Board
PC-299 Board
5.1.3.2 PC-299 Ethernet Microprocessor/A-D Board
PC-299 Board with Cable Connections
5.1.3.3 Valve Manifold Position Detector Circuit
5.1.3.4 Scanner Front Panel LED Assembly
See drawings Figures 5.7a, 5.7b, and 5.7c
Figure 5.7c
9816 Scanner with
4 Slide the front panel forward as far as it will go approximately 3/8
5.1.4 Replacement of Transducers
Top View of DH200
The hex-head standoff screws used on DH200 positions 2 and
be over tightened or else the screw may break
5.1.5 Model 9816 Solenoid Replacement
Figure 5.9 and Figure 5.9a
Schematic of 9816 Solenoids
Figure 5.9a Solenoids Attached to Module
5.1.6 Replacement of O-Rings
5.1.6.1 DH200 Pressure Transducer O-Ring Replacement
DH200 Transducer O-Ring Replacement
5.1.6.2 Tubing Plate O-Ring Replacement
5.1.6.3 Adapter Plate O-Ring Replacement
5.1.6.4 Calibration Manifold Piston O-Ring Replacement
5.1.6.5 Solenoid Valve O-Ring Replacement
Solenoid Valve O-Ring Replacement
5.1.6.6 Module Rear Manifold O-Ring Replacement
For glued O-ring replacement
For non-glued flared post O-ring replacement
For all
5.1.6.7 Solenoid Valve O-Ring Replacement
Page
5.1.6.9 Supply Air and Purge Air Sensing Transducers
As you are looking at the pneumatic backplane, the two
the pressure rating of the supply-sensing transducer is 150 psi
The pressure rating of the purge-sensing transducer is 750 psi and
5.1.7 Front Pull-out Slide Tray
5.2 Upgrading Module Firmware
5.2.1 Upgrading Firmware via Host TCP/IP Port
Update Firmware Screen
6.1 98RK-1 Scanner Interface Rack and Module Troubleshooting
Chapter Troubleshooting Guide
6.1.1 Checking 98RK-1 Scanner Interface Rack Power-up Sequence
6.1.2 Checking Module LED Power-Up Sequence
6.1.3 Checking Module TCP/IP Communications
6.1.3.1 Module IP Address Assignment
6.1.3.2 Host IP Address Assignment for Windows Operating Systems
6.1.3.3 Troubleshooting with NUSS NetScanner Unified Startup Software
6.1.3.4 Verifying Host TCP/IP Communications
6.2 Zero and Gain Calibration Troubleshooting
98RK-1 SUPPLY air transducer. Verify the valve position through the ‘q0B’ command and front panel LEDs. This command reflects the actual sensed calibration valve position in the Model 9816 Intelligent Pressure Scanner
Chapter Start-up Software 7.1 Introduction
Appendix A Cable Design
NetScanner Ethernet Interface Cable 9082 Cable
Appendix B NetScanner System Range Codes
Range Code
Full Scale Pressure
Minimum Calibration
20 psid
Appendix C Creating a Shortcut Icon
Select the executable file, in this case the NUSS file, with one left-click of the mouse, and a drop-down menu will appear
Appendix D Merchandise Return Procedure
Bill To and Ship To address
Measurement Specialties, Inc 34 Research Drive Hampton, VA USA
Phone 757 Toll Free 800 Fax 757 E-mail sales@PressureSystems.com