RoboteQ AX500 manual Encoder Error Detection and Protection, Adding Safety Limit Switches

Models: AX500

1 154
Download 154 pages 41.77 Kb
Page 68
Image 68

Closed Loop Position Mode

3.Loosen the sensor’s axle from the motor assembly.

4.Launch the Roborun utility and click on the Run tab. Click the “Start” button to begin communication with the controller. The sensor values will be displayed in the Ana1 and Ana2 boxes.

5.Move the sensor manually to the middle position until a value of “0” is measured using Roborun utility

6.Verify that the motor sliders are in the “0” (Stop) position. Since the desired posi- tion is 0 and the measured position is 0, the controller will not attempt to move the motors. The Power graph on the PC must be 0.

7.Apply power to the Motor Power input (Vmot terminals). The motor will be stopped.

8.With a hand ready to disconnect the Motor Power cable or ready to press the “Pro- gram” and “Set” buttons at the same time (Emergency Stop), SLOWLY move the sensor off the center position and observe the motor’s direction of rotation.

9.If the motor turns in the direction in which the sensor was moved, the polarity is correct. The sensor axle may be tighten to the motor assembly.

10.If the motor turns in the direction away from the sensor, then the polarity is reversed. The wire polarity on the motors should be exchanged. If using a potenti- ometer as sensor, the GND and +5V wires on the potentiometer may be swapped instead.

11.Move the sensor back to the center point to stop the motor. Cut the power if con- trol is lost.

12.If the polarity was wrong, invert it and repeat steps 8 to 11.

13.Tighten the sensor.

Important Safety Warning

Never apply a command that is lower than the sensor’s minimum output value or higher than the sensor’s maximum output value as the motor would turn forever try- ing to reach a position it cannot. For example, if the max position of a potentiometer is 4.5V, which is a position value of 114, a destination command of 115 cannot be reached and the motor will not stop.

Encoder Error Detection and Protection

The AX500 contains an Encoder detection and protection mechanism that will cause the controller to halt if no motion is detected on either Encoder while a power level of 25% or higher is applied to the motor. If such an error occurs, the controller will halt permanently until its power is cycled or it is reset.

Adding Safety Limit Switches

The Position mode depends on the position sensor providing accurate position information.

If the potentiometer is damaged or one of its wire is cut, the motors may spin continuously

68

AX500 Motor Controller User’s Manual

Version 1.9b. June 1, 2007

Page 68
Image 68
RoboteQ AX500 manual Encoder Error Detection and Protection, Adding Safety Limit Switches