12-6-6. Erroneous Flame-Out Condition

Disconnect heating gas valve (GV1, CN08) connector, and measure resistance at connector.

Normal

WHT – WHT 1 – 2.5 kΩ

* Use a circuit tester (set to Ω range).

In case of abnormality Replace heating electromagnetic valve.

3) Check electromagnetic valve (GV2) of the combination gas valve.

Measure DC voltage at electromagnetic valve connector (CN08) (under heating operation, during combustion).

Normal

ORG – ORG DC 90 – 120 V

*Use a circuit tester (set to DC range).

In case of abnormality Replace outdoor unit PCB.

Disconnect heating electromagnetic valve connector (CN08), and measure resistance at connector.

Normal

ORG – ORG 1 – 2.5 kΩ

* Use a circuit tester (set to Ω range).

In case of abnormality Replace heating electromagnetic valve.

4) Check proportional control valve (PV).

Measure DC voltage at proportional valve connector (CN11) (under heating operation, during combustion).

Normal

BLU – BLU DC 5 – 30 V

*Use a circuit tester (set to DC range).

In case of abnormality Replace outdoor unit PCB.

5) Check flame rod.

Check if flame rod connector (CN17, 1P) is connected properly.

Measure AC voltage between flame rod connector and ground.

Normal

AC 104 – 126 V

*Use a circuit tester (set to AC range).

In case of abnormality Replace flame rod.

Disconnect flame rod connector (CN17) and measure direct current at connector.

Normal

DC 2µA or more

*Use a circuit tester (set to DC range).

In case of abnormality Replace flame rod.

12-6-6. Erroneous Flame-Out Condition

Failure Display on Outdoor Unit PCB: ● ● ● ●

Check in same manner as “Failure Display● ● ● ●.”