12-3-2. Thermistor Abnormality (Indoor Unit Only)
Check open / short circuit at the coil thermistor and room thermistor (between 1 and 2 of the lamp 8P) on the PCB of the indoor unit (but only when the room temperature is 14 to 113°F).
Check the following according to the failure display. Check items listed in
●light off
●light on
No. | Caused by (outdoor unit) | LED lamps | Meaning | ||||
2 | 3 | 4 | 5 | ||||
|
|
| |||||
— | Normal | ● ● ● ● | Normal operation | ||||
|
|
|
| ||||
— | Defective in IC chip (E 2PROM) | ● ● ● ● | Cannot read IC chip data or missing IC chip on outside | ||||
|
|
|
|
|
| PCB | |
|
|
|
| ||||
— | Defective Gas Valves | ● ● ● ● | Detects abnormality in Gas Valve Circuit at initial | ||||
|
|
|
|
|
| checking | |
A | Detective Thermistor 1 | ● ● ● ● | Open or Short of Thermistor 1 | ||||
|
|
|
| ||||
B | Detective Thermistor 2 | ● ● ● ● | Open or Short of Thermistor 2 | ||||
|
|
|
| ||||
C | Limit switch | ● ● ● ● | Thermal fuse or Bimetal Thermostat tripped | ||||
|
|
|
| ||||
D | Flame current circuit | ● ● ● ● | Defective abnormal in Flame Current Circuit | ||||
|
|
|
| ||||
E | Lighting failure | ● ● ● ● | Couldn’t establish flame | ||||
|
|
|
| ||||
F | Lost flame | ● ● ● ● | Flame Sensor Circuit detects lost flame and could not | ||||
|
|
|
|
|
| establish the flame | |
|
|
|
| ||||
G | Incorrect combustion motor speed | ● ● ● ● | Incorrect combustion motor speed | ||||
|
|
|
| ||||
H | ● ● ● ● | Thermistor 1 or Thermistor 2 temperature did not go | |||||
|
|
|
|
|
| down in set period | |
|
|
|
| ||||
I | Over number of times in retry | ● ● ● ● | Combustion stopped by Thermistor 1 or Thermistor 2 | ||||
|
|
|
|
|
| more than set number | |
|
|
|
| ||||
J | Bypass Valve (V2) not open | ● ● ● ● | Bypass Valve failure or | ||||
|
|
|
| ||||
— | Reversing Valve not working | ● ● ● ● | Reversing Valve failure, | ||||
|
|
|
|
|
| shortage of refrigerant | |
|
|
|
|
|
|
|
Note: Refer to
12-3-4. CT Detection (Refer to 12-3-9 and 12-3-10.)
(1)Compressor abnormality
(2)Compressor