8-3. Heating

8-3. Heating

8-3-1. Room Temperature Control

Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the indoor unit.

All information is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit.

 

 

 

Thermo.

 

Thermo.

 

 

Thermo.

OFF

 

OFF

Set temp.

 

ON

 

 

Thermo.

 

 

 

ON

 

 

 

 

T+2°F

 

 

 

 

 

T+1°F

 

 

 

 

 

More than

 

 

 

More than

3 minutes

3 minutes

3 minutes

3 minutes

 

 

 

 

Compressor

OFF

 

OFF

 

OFF

Combustion

OFF

 

OFF

 

OFF

Reversing

OFF

 

 

 

 

valve coil

 

 

 

 

 

 

 

30

 

30

 

 

 

sec.

 

sec.

Indoor fan

OFF LL

Set

LL

Set speed

speed

Indoor heat exch. coil temp.

113°F (45°C)

90°F (32°C)

Operation button OFF

The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.

As a protective measure, the control circuit switches the compressor OFF after 3 minutes or more of com- pressor operation.

Thermo. ON: When the room temperature is below T + 1°F (T°F is set temperature).

Compressor ON

Thermo. OFF: When the room temperature is equal to or below set temperature T + 2°F. Compressor OFF