8-3. Heating
8-3-1. Room Temperature Control
●Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the indoor unit.
●All information is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit.
|
|
| Thermo. |
| Thermo. | |
|
| Thermo. | OFF |
| OFF | |
Set temp. |
| ON |
|
| Thermo. | |
|
|
| ON | |||
|
|
|
| |||
T+2°F |
|
|
|
|
| |
T+1°F |
|
|
|
|
| |
More than |
|
|
| More than | ||
3 minutes | 3 minutes | 3 minutes | ||||
3 minutes | ||||||
|
|
|
| |||
Compressor | OFF |
| OFF |
| OFF | |
Combustion | OFF |
| OFF |
| OFF | |
Reversing | OFF |
|
|
|
| |
valve coil |
|
|
|
| ||
|
|
| 30 |
| 30 | |
|
|
| sec. |
| sec. | |
Indoor fan | OFF LL | Set | LL | Set speed | ||
speed |
Indoor heat exch. coil temp.
113°F (45°C)
90°F (32°C)
Operation button OFF
●The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a
●As a protective measure, the control circuit switches the compressor OFF after 3 minutes or more of com- pressor operation.
●Thermo. ON: When the room temperature is below T + 1°F (T°F is set temperature).
Compressor ➔ ON
●Thermo. OFF: When the room temperature is equal to or below set temperature T + 2°F. Compressor ➔ OFF
33