Siemens 7ML19985AB01 instruction manual Transducer, Temperature Sensor, Cabling

Models: 7ML19985AB01

1 112
Download 112 pages 47.88 Kb
Page 11
Image 11

Battery:

» 9 V (ANSI / NEDA 1604, PP3 or equivalent) or

 

3V lithium battery

TRANSDUCER

 

Model:

» XRS-5*

 

Refer to associated Transducer manual.

TEMPERATURE SENSOR

Model:

» TS-2, LTS-1 or LTS-1C

 

Refer to associated Temperature Sensor manual.

CABLING

 

 

Transducer:

 

» RG-62U coaxial

 

 

» maximum separation 183 m (600 ft)

 

 

» must be run in grounded metal conduit

mA Output:

 

» Belden 8760 or equivalent

Synchronisation:

 

» Belden 8760

Temperature Sensor:

» Belden 8760, 1 pair shielded/twisted,

 

 

18 AWG or equivalent

 

 

» maximum separation 183 m (600 ft)

 

 

» can be run in conduit with transducer cable

Communication:

» RS-232:

» Belden 8770, 3 wire shielded, 24 AWG

 

 

or equivalent

 

 

» maximum separation 15 m (50 ft)

 

» Bipolar Current:

» Belden 9552, 2 pair shielded/twisted,

 

 

18 AWG or equivalent

» maximum separation 1,500 m (5,000 ft)

*Note: The XRS-5 must be used with the TS-2 external temperature sensor when operating with the OCM-3.

Velocity Input:

» Belden 8760 or equivalent

7ML19985AB01

OCM III

11

Page 11
Image 11
Siemens 7ML19985AB01 instruction manual Transducer, Temperature Sensor, Cabling