Siemens 7ML19985AB01 Damping, For battery operation, set display lighting to off or auto

Models: 7ML19985AB01

1 112
Download 112 pages 47.88 Kb
Page 29
Image 29

Flow Rate Field

flow rate

units, P5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Totalizer Field

total

multiplier, P32

Relay / No Echo Field

relay identification

under loss of echo condition, "NO ECHO" will alternately flash

Status Field

relay status : 0 = relay de-energized 1 = relay energized

* = alarm state (indicated when flashing)

The OCM-3 provides illumination for the LCD for easier viewing of the display. Illumination can be set (P14) to be normally on or off, or automatic. When automatic is selected, the lighting will automatically go on when keypad activity is sensed and then extinguish after 15 seconds of inactivity.

For battery operation, set display lighting to off or auto.

DAMPING

The OCM-3 provides two separate damping functions: reading and mA output. Zero or no damping allows fastest response while high or 100% provides the slowest response. The damping is usually set to provide a reliable response without sacrificing stability.

The reading damping, P13, dampens only the flow rate reading of the ‘Flow and Total’ display F2. The damping selections are: off, low, medium and high. Relay functions associated with flow rate respond to the dampened reading values.

mA output damping, P27, dampens the change in the mA output. The parameter entry is in seconds for spanning the 0 to 100% of the mA range selected (P26). Displays and relay functions associated with the mA output respond to its

dampened value.

7ML19985AB01

OCM III

29

Page 29
Image 29
Siemens 7ML19985AB01 instruction manual Damping, For battery operation, set display lighting to off or auto