POWER CONNECTIONS

The OCM-3 power supply accepts 100, 115, 200 or 230 V ac per switch SW1 (board B) selection and 9 to 30 V dc.

The OCM-3 operates either under ac or dc power, or both ac and dc live simultaneously. If both ac and dc power are live, the OCM-3 normally draws power from the ac supply. In the event that the ac supply fails, the OCM-3 then draws power from the dc supply.

AC POWER

*

* switch shown in

 

‘OFF’ position,

 

select appropriate

 

voltage.

100/115/200/230 V ac, 50/60 Hz, select voltage via switch on board B

The equipment must be protected by a 15 A fuse or

circuit breaker in the building installation.

A circuit breaker or switch in the building installation, marked

as the disconnect switch, shall be in close proximity to the equipment and within easy reach of the operator.

DC POWER

negative dc input (TB1-24) is

9 to 30 Volttied to ground (TB1-34) dc input

dc terminals shall be supplied from SELV source in accordance with IEC 1010-1 Annex H.

19

OCM III

7ML19985AB01

Page 19
Image 19
Siemens 7ML19985AB01 instruction manual Power Connections, AC Power, DC Power