Command Interface

5.2.20Read_Extended_Parameter_Echo_List

Purpose

When the parameters are transferred to the AS-i slaves, they return ªecho valuesº as the response. The read parameter echo list call reads out the echo values of all AS-i slaves.

Structure of the Job Data in the Send Buffer

Bank

2

2

Byte

0

1

Meaning

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

 

 

 

 

 

 

 

 

Command number: 33 H

00H

Structure of the Job Data in the Receive Buffer

Bank

2

2

Byte

0

1

Meaning

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Echo of the command number 33 H

Command status

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

3

3

3

3

3

3

3

3

2

3

4

5

6

7

8

9

10

11

12

13

14

15

0

1

2

3

4

5

6

7

8

irrelevant

Par echo slave 2

Par echo slave 4

Par echo slave 6

Par echo slave 8

Par echo slave 10

Par echo slave 12

Par echo slave 14

Par echo slave 16

Par echo slave 18

Par echo slave 20

Par echo slave 22

Par echo slave 24

Par echo slave 26

Par echo slave 28

Par echo slave 30

irrelevant

Par echo slave 2B

Par echo slave 4B

Par echo slave 6B

Par echo slave 8B

Par echo slave 10B

Par echo slave 12B

Par echo slave 1

Par echo slave 3

Par echo slave 5

Parameters slave 7

Par echo slave 9

Par echo slave 11

Par echo slave 13

Par echo slave 15

Par echo slave 17

Par echo slave 19

Par echo slave 21

Par echo slave 23

Par echo slave 25

Par echo slave 27

Par echo slave 29

Par echo slave 31

Par echo slave 1B

Par echo slave 3B

Par echo slave 5B

Parameters slave 7B

Par echo slave 9B

Par echo slave 11B

Par echo slave 13B

SIMATIC NET CP 243-2 AS-i Master

5-45

C79000-G8976-C142/02

Page 113
Image 113
Siemens CP 243-2 installation instructions ReadExtendedParameterEchoList