Access to the Data of the AS-i Slaves

3.1Access to the Binary Data of the AS-i Slaves

3.1.1Addressing the AS-i Slaves in the User Program

Requirements

Before you can access the I/O data of the AS-i slaves, the following requirements must be met:

SDeactivate the filtering of the analog inputs for the CP 243±2 in the system data block of the S7±200 CPU.

SSet the ªPLC_RUNº bit (bit 7) in the digital control byte to '1' at the beginning of the cyclic program.

SAccess to the I/O data of the slaves is then only allowed when the ªCP_Readyº bit (bit 1) in the digital status byte is set to '1'.

Access to the Binary Values

The CP 243-2 assigns four bits (a nibble) in the input and output data area for each AS-i slave. The PLC can write (slave output data) and read (slave input data) this nibble.

This allows bi-directional slaves to be addressed.